Extension of Budeanu’s Power Theory for Three-Phase Three-Wire Systems Supplied by Symmetrical Nonsinusoidal Voltages Using the Currents’ Physical Components Theory
Zbigniew Sołjan, Tomasz Popławski, Dariusz Sajewicz
Key points
From the paper's conclusion- The analysis is restricted to 3-p 3-w circuits fed by symmetrical nonsinusoidal voltages and loaded with linear time-invariant (LTI) elements, which are not sources of harmonics; consequently, it does not directly address asymmetrical supply conditions, four-wire systems, time-varying loads, or nonlinear loads with harmonic generation.
Abstract
This paper presents a theoretical and numerical extension of Budeanu’s power theory for three-phase three-wire systems supplied by symmetrical nonsinusoidal voltages and feeding unbalanced linear time-invariant loads. The proposed formulation combines the classical Budeanu framework with the Currents’ Physical Components (CPC) theory to provide a physical interpretation of Budeanu distortion power. Five mutually orthogonal components of the load current are distinguished, namely the active, scattered, Budeanu reactive, Budeanu-complemented reactive, and negative-sequence unbalanced currents. Consequently, Budeanu distortion power is shown to be an orthogonal combination of three powers (scattered, Budeanu-complemented reactive, and negative-sequence unbalanced) and not merely a residual obtained from the apparent, active, and reactive powers. The theoretical formulation is verified numerically using three illustrative delta-connected load configurations fed by a voltage composed of the 1st, 5th, and 7th harmonics. In all examples, the sum of the proposed components reproduces exactly the line currents calculated directly with Ohm’s law and Kirchhoff’s current law, and they distinguish the physical mechanisms responsible for each contribution to distortion power. The analysis is restricted to 3-p 3-w circuits fed by symmetrical nonsinusoidal voltages and loaded with linear time-invariant (LTI) elements, which are not sources of harmonics; consequently, it does not directly address asymmetrical supply conditions, four-wire systems, time-varying loads, or nonlinear loads with harmonic generation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Unified Power Theory of Electric Circuits Driven by Non-Sinusoidal Periodic Voltage and Current Sources Developed Using Inner-Exterior Product VectorsEnergies · 2026
- Cross-Order Distortion Descriptor (CDD) for Paired Voltage and Current Harmonic Spectra: Separating THD-Determined and Order-Dependent PartsElectronics · 2026
- Methods for Determining the Actual Contributions of Consumers to the Voltage Unbalance of a Three-Phase NetworkElectricity · 2026
- Comparison of Total Harmonic Distortion (THD) in Three-Level, Three-Phase Inverters Using Cascaded H-Bridge (CHB) and Neutral-Point-Clamped (NPC) TopologiesKufa Journal of Engineering · 2026
- Evaluation of Electromagnetic Performances of Three Parallel Cable Systems and a Busbar System Used in Power Distribution Network Under High THD Harmonic Loading with FEMEnergies · 2026
- Research on Zero-Crossing Distortion Suppression Method for Three-Phase Line-Voltage Cascaded Boost High Power Factor RectifierElectronics · 2026