Experimental Investigation of Air Cooling and Humidification by a Wetted Porous-Clay-Duct Earth–Air Heat Exchanger in a Hot-Arid Greenhouse

Osamah Alanazi, Rabah Boukhanouf, Mohammed Aldakhil

Key points

From the paper's conclusion
  • A wetted porous-clay-duct earth–air heat exchanger (EAHE) supplied with outdoor air was tested in a 360 m2 experimental greenhouse in Al-Kharj, Saudi Arabia, during 22 July–11 August 2026.

Abstract

A wetted porous-clay-duct earth–air heat exchanger (EAHE) supplied with outdoor air was tested in a 360 m2 experimental greenhouse in Al-Kharj, Saudi Arabia, during 22 July–11 August 2026. Over 21 days of continuous operation, the discharge air averaged 29.20 °C (range 24.3–36.0 °C; 96.2% of 30,117 one-minute records at or below 34 °C) with no upward drift, while the greenhouse centre averaged 40.53 °C and peaked at 64.6 °C. A partially shaded, unaspirated logger beside the supply fan read on average 10.57 K above the discharge, rising to 19.12 K above discharge during the daytime; comparison with airport records indicates that it may over-read by up to about 10 K at the daily peak. The discharge air carried about 4.4 g/kg more water than the intake-side air, day and night. Across scenarios combining 0–10 K intake bias with centreline-to-mean velocity ratios of 1.0–1.4, the daytime gross sensible rate was 5.38–15.79 kW and the moist-air enthalpy-decrease rate −1.52 to +6.84 kW, the upper values corresponding to no bias and a uniform velocity profile. At night, the discharge air gained enthalpy. Soil temperature and clay moisture were not measured, so the contribution of wetting cannot be isolated.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers