Key points
From the paper's conclusion- The variations in heating capacity, coefficient of performance (COP), and discharge temperature of both single-stage and quasi-two-stage heat pumps were compared and analyzed under diverse winter climatic conditions, and the energy-saving and environmental benefits of the system were evaluated.
Abstract
Air-source heat pumps suffer from significant performance degradation under low-temperature and humid-cold conditions, which restricts their adoption for clean heating across various climate zones in China. In this study, an experimental test platform was developed using a conventional single-stage air-source heat pump as a reference. Five representative cities were selected, covering severe-cold, cold, and hot-summer–cold-winter climate zones, and the winter temperature and humidity conditions of each city were simulated to replicate the corresponding ambient operating conditions. The variations in heating capacity, coefficient of performance (COP), and discharge temperature of both single-stage and quasi-two-stage heat pumps were compared and analyzed under diverse winter climatic conditions, and the energy-saving and environmental benefits of the system were evaluated. Compared with its single-stage counterpart, the quasi-two-stage air-source heat pump demonstrates an improvement in heating capacity ranging from 2.8% to 13.7% and an increase in COP between 0.6% and 7.3%. The energy-saving advantages are particularly pronounced in severe-cold regions. In the humid and cold areas of southern China, this technology effectively addresses the challenges of high energy consumption and insufficient heating capacity. Furthermore, the quasi-two-stage air-source heat pump system helps reduce power consumption during the heating season, thereby lowering carbon emissions and pollutant discharges associated with thermal power generation. This study provides experimental evidence to support the optimization and broader implementation of low-temperature heat pumps.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Simulation Study on the Performance Assessment of a Direct-Expansion Solar PV/T Coupled Air-Source Heat Pump System for Rural Buildings in Typical Climate Zones of ChinaBuildings · 2026
- A Review on Performance Optimization and Relevant Application Research of Heat Pump Technologies for Energy System DecarbonizationMachines · 2026
- Performance analysis and multi-objective optimization of PV/T coupled transcritical CO2 heat pump under wide temperature range conditionsEnergy · 2026
- Experimental study on space heating performance of PVT-air dual heat source direct expansion heat pump system based on micro heat pipe arraysRenewable Energy · 2026
- Comparative energy, economic, and environmental assessment of a flexible heat pump using the low-GWP refrigerant R-1234yfJournal of Cleaner Production · 2026
- High-Temperature Water-to-Water Heat Pumps for the Retrofit of a Residential ComplexBuildings · 2026