Energies

Forecast-Driven, Energy-Based, and Degradation-Aware Energy Management for a Photovoltaic-Integrated Hybrid UPS with a Dedicated Grid Battery Charger

Rafael Ruben Boros, Ádám Móré, Zoltán Kovács

Key points

From the paper's conclusion
  • The results demonstrate traceable, validation-gated comparisons while showing that maintained operational feasibility does not guarantee an economic advantage under PV forecast mismatch.

Abstract

This paper presents a forecast-plan/actual-replay energy management framework for a photovoltaic-integrated hybrid uninterruptible power supply. A day-ahead schedule is generated from forecasts and replayed using realized profiles. The formulation accounts for converter losses, LiFePO4 battery degradation, reserve requirements, and terminal stored-energy constraints. Economic comparisons require terminal inventory comparability and critical validation compliance. Ten baseline 24 h scenarios cover positive and negative prices, photovoltaic forecast error, alternative objectives, and unannounced outages. Five additional cases examine prescribed PV overprediction and underprediction. Relative to a terminal-comparable grid-first UPS, system-level selected-objective cost reductions reached 15.818% in the positive-price PV case and 31.010% in the PV-rich outage case; these values do not isolate predictive scheduling or GA effects. In the five additional cases, selected-objective differences ranged from a 0.673% reduction to a 1.232% increase, despite preserved feasibility and complete load service in the primary runs. Null and control cases showed no artificial cycling. The non-compliant baseline case and additional diagnostic runs were excluded from economic inference. The results demonstrate traceable, validation-gated comparisons while showing that maintained operational feasibility does not guarantee an economic advantage under PV forecast mismatch.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Forecast-Driven, Energy-Based, and Degradation-Aware Energy Management for a Photovoltaic-Integrated Hybrid UPS with a Dedicated Grid Battery Charger — Science Skim