Energies

Fast Identification of Static Voltage Weak Nodes in Large-Scale Power Grids Using GATv2-JK

Zhencheng Liang, Siying Wang, Junhui Liu, Bin Li, Biyun Chen, Peijie Li

Key points

From the paper's conclusion
  • These results indicate that the framework prioritizes weak buses while substantially reducing the number of CPF re-verifications required under the studied low-margin conditions.

Abstract

Rapid identification of static voltage weak buses in large-scale power grids is hindered by the computational burden of bus-by-bus continuation power flow (CPF) verification. This study proposes a GATv2–Jumping Knowledge (GATv2-JK) framework that screens operating conditions by system voltage stability margin and uses CPF-derived bus load margins to supervise weak-bus scoring. GATv2 attention, multi-hop feature fusion, and a local ranking constraint prioritize high-risk buses; a validation-calibrated adaptive strategy selects candidates for CPF re-verification. A dataset of 400 operating conditions with system margins below 15% was constructed from a practical 2475-bus grid containing 333 positive-load buses. Buses with CPF load margins below 10% were labeled as weak. On the test set, the model achieved an area under the precision–recall curve (AUC-PR) of 0.8002 and a Recall@20 of 0.9478. Under the adaptive CVaR0.95 setting, it selected 17.22 buses per condition on average (5.17% of positive-load buses) and attained a sample-averaged recall of 0.9863. These results indicate that the framework prioritizes weak buses while substantially reducing the number of CPF re-verifications required under the studied low-margin conditions.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Fast Identification of Static Voltage Weak Nodes in Large-Scale Power Grids Using GATv2-JK — Science Skim