Energies

Stability Assessment and Damping Control for Grid-Forming Wind-Storage Systems with DC-Side Coupling Dynamics

Juping Gu, Yang Qu, Shun Sang, Yaxin Wang, Wangyu Xu, Xiaocen Xue, Liang Hua

Key points

From the paper's conclusion
  • Current stability research commonly concentrates on turbine-grid interactions, yet overlooks coupling dynamics at the DC-link, which motivates this study to establish a quantitative stability evaluation approach for grid-forming wind-storage systems with DC-side coupling taken into consideration.

Abstract

This work develops a grid-forming control framework integrated with supplementary energy storage, so that permanent-magnet direct-drive wind turbines can deliver primary frequency regulation and inertial support services. Current stability research commonly concentrates on turbine-grid interactions, yet overlooks coupling dynamics at the DC-link, which motivates this study to establish a quantitative stability evaluation approach for grid-forming wind-storage systems with DC-side coupling taken into consideration. Small-signal impedance representations are firstly constructed for the machine-side converter (MSC), grid-side converter (GSC), and energy-storage converter with respect to the DC-link. On this basis, quantitative investigation is carried out to clarify how grid stiffness, inertia coefficient, droop gain, as well as charging/discharging operating modes of energy storage shape the DC-side stability margin of the hybrid system. To boost DC-link electrical damping, a supplementary stabilizing control scheme is embedded within the control loops of the energy-storage converter. Simulation outcomes reveal that the inertial support loop may inject negative damping and impair DC-link stability. Besides, discharging operation yields better stability performance for the wind-storage configuration relative to the charging condition. The devised stabilizing controller is capable of strengthening DC-side stability, enabling simultaneous inertial response and primary frequency support. Validations based on the PSCAD/EMTDC environment confirm the accuracy of theoretical deductions and the practical performance of the presented control solution.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Stability Assessment and Damping Control for Grid-Forming Wind-Storage Systems with DC-Side Coupling Dynamics — Science Skim