Strategies to Mitigate Reverse Power Flow in Distribution Networks with High Penetration of Solar Photovoltaic Generation
Ivan Santos Pereira, Gustavo da Costa Vergara, Jesús M. López-Lezama, Nicolás Muñoz-Galenao, Lina Paola Garcés Negrete
Universidade Federal de Goiás · Universidad de Antioquia
Key points
From the paper's conclusion- The quantitative results demonstrate that BESS allocation was the superior strategy, reducing technical losses by 61.3% and fully mitigating reverse power flow under steady-state conditions.
Abstract
The power industry has undergone significant recent changes due to the growing demand for a cleaner and more sustainable energy mix. In this context, the Brazilian government began encouraging distributed generation (DG), making photovoltaic generation a strong trend in the country. However, the expansion of DG may cause negative impacts on the grid, such as reverse power flow (RPF) and overvoltages, which motivates research aimed at mitigating these effects. This study proposes strategies to mitigate RPF in distribution networks with high penetration of photovoltaic generation and evaluates their impacts on the electrical system. Three strategies were analyzed: a battery energy storage system (BESS), a control mechanism using a Grid Zero inverter, and PV Curtailment. The strategies were implemented in OpenDSS on a real distribution network located in São Paulo, Brazil. The assessment involved analyzing power flow in critical transformers and at the substation, as well as monitoring bus voltages and network energy losses. The quantitative results demonstrate that BESS allocation was the superior strategy, reducing technical losses by 61.3% and fully mitigating reverse power flow under steady-state conditions. The Grid Zero inverter eliminated power injection into the grid; however, it increased substation dependency by 59% compared to the baseline scenario. PV curtailment, although achieving the smallest reduction in RPF, proved to be the most effective technique for power quality, limiting the average voltage rise to 0.7%.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- ADBO-Optimized Smart Inverter Integration of PV/BESS for Incremental EV Charging Capacity Without Further Voltage Degradation on a Gaborone-Oriented IEEE 69-Bus Surrogate FeederEng · 2026
- Selective fairness-based inverter coordination for curtailment equity and voltage regulation in highly PV penetrated distribution networkEngineering Research Express · 2026
- Probabilistic BESS Scheduling for Duck-Curve Mitigation Under Correlated DER Penetration in Distribution SystemsMathematics · 2026
- Service adaptability assessment and coordinated planning and operation of PV-rich low-voltage active distribution network clustersFrontiers in Energy Research · 2026
- Voltage Control and Governance Strategies for Distributed Photovoltaic Integration into Distribution Networks Based on Intelligent Dynamic Voltage-Coordinated GridApplied Sciences · 2026
- Optimal locations and capacities of multiple BESSs in a RES-integrated distribution network: a real-world case studyScientific Reports · 2026