Coordinated Voltage and Power Factor Optimization in EV- and DER-Integrated Distribution Systems Using an Adaptive Rolling Horizon Approach
Wonjun Yun, Phi-Hai Trinh, Jhi‐Young Joo, Il‐Yop Chung
Kookmin University · Lawrence Livermore National Laboratory
Key points
From the paper's conclusion- To address these issues, this paper proposes a two-stage adaptive rolling horizon (ARH)-based model predictive control (MPC) framework for coordinated voltage and power factor (PF) control in distribution systems.
Abstract
The penetration of distributed energy resources (DERs), such as photovoltaic (PV) generation and electric vehicles (EVs), in distribution systems has been increasing rapidly. At the same time, load demand is rising due to the proliferation of data centers and the growing use of artificial intelligence. These trends have introduced new operational challenges: reverse power flow from PV generation during the day and low-voltage conditions during periods of peak load or when PV output is unavailable. To address these issues, this paper proposes a two-stage adaptive rolling horizon (ARH)-based model predictive control (MPC) framework for coordinated voltage and power factor (PF) control in distribution systems. The proposed framework, designed from the perspective of a distributed energy resource management system (DERMS), integrates EV charging and discharging scheduling with PV- and EV-connected inverter control. In the first stage, the ARH method optimizes EV charging and discharging schedules to regulate voltage levels. In the second stage, optimal power flow analysis is employed to adjust the voltage of distribution lines and the power factor at the substation through reactive power compensation, using PV- and EV-connected inverters. The proposed algorithm aims to maintain stable operation of the distribution system while minimizing PV curtailment by computing optimal control commands based on predicted PV generation, load forecasts, and EV data provided by vehicle owners. Simulation results on the IEEE 37-bus test feeder demonstrate that, under predicted PV and load profiles, the system voltage can be maintained within the normal range of 0.95–1.05 per unit (p.u.), the power factor is improved, and the state-of-charge (SOC) requirements of EV owners are satisfied. These results confirm that the proposed framework enables stable and cooperative operation of the distribution system without the need for additional infrastructure expansion.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Hierarchical Deep Reinforcement Learning and Model Predictive Control for Voltage-Aware Electric Vehicle Charging Coordination in Distribution NetworkIEEE Access · 2026
- Economic Dispatch and Voltage‐Reactive Power Coordinated Control for Active Distribution Networks With Virtual‐Physical Hybrid Energy StorageInternational Transactions on Electrical Energy Systems · 2026
- A Novel Utilization Factor‐Based Adaptive Coordination Strategy for Electric Vehicle‐to‐Grid and Energy Storage in Peak Load ManagementEnergy Storage · 2026
- Coordinated dual layer volt-var control for power distribution systems with electric vehicles and distributed generationsInternational Journal of Emerging Electric Power Systems · 2026
- Integration of renewable energy of solar PV and wind for the optimal charging and discharging of plug-in electric vehiclesSolar Compass · 2026
- Smart energy strategies for dynamic EV charging and renewable integration in distribution systems: A multi-objective optimization frameworkEnergy Strategy Reviews · 2026