Objective-Dependent Harmonic Monitoring Under Variable Load: Global and Load-Stratified Prioritization of Current Harmonic Records

Franjo Pranjić, Peter Virtič

Key points

From the paper's conclusion
  • The results indicate that much of the disagreement between global absolute and relative rankings is associated with load variation and the normalization denominator.

Abstract

Under variable load, ranking harmonic monitoring intervals by absolute current magnitude or fundamental-normalized amplitude can prioritize different operating conditions. This study evaluates equal-budget load-conditioned ranking using two non-simultaneous monitoring campaigns in a public building: 1138 ten-minute records at the point of common coupling (PCC) and 1010 at an internal distribution board (IDB). Six harmonic orders across three phases were examined. For the fifth harmonic on L3, global top-10% rankings shared 5/114 records (4.4%) at the PCC and 12/101 (11.9%) at the IDB. Allocating the same selection budget across 10 root mean square (RMS) current strata increased these overlaps to 84/114 (73.7%) and 82/101 (81.2%). Stratification by fundamental current yielded similar results. Randomly reassigned strata did not reproduce this increase (95th percentile overlap: 7.5% and 13.9%, respectively). Agreement generally increased across all six phase–campaign contexts, although the magnitude varied. The results indicate that much of the disagreement between global absolute and relative rankings is associated with load variation and the normalization denominator. These findings concern one building and two short, non-simultaneous campaigns separated by over 2 years. Joint reporting of absolute and relative harmonic magnitudes, together with load-conditioned comparisons, supports transparent monitoring record prioritization without implying fault detection, harmonic source attribution, or changes to standards-based compliance assessment.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Objective-Dependent Harmonic Monitoring Under Variable Load: Global and Load-Stratified Prioritization of Current Harmonic Records — Science Skim