Physics-Informed Multi-Agent Transient Voltage Support with Simplified UHVDC Receiving-End Characteristics
Xi Ye, Yongcan Wang, Wei Liu, Caibin Zhang, Jiayu Bai, Zongsheng Zheng, Chufang Xu
Key points
From the paper's conclusion- On the IEEE 39-bus benchmark, with all controllers sharing one receiving-end model and identical actuator limits, the PIML-agent reduces the receiving-area voltage deviation integral by 87.67–97.48% relative to no control and 76.95–94.84% relative to local rule-based support across six fault, load, delayed-support, corridor, and UHVDC-recovery scenarios, and its six-scenario mean by 60.05% relativ
Abstract
This paper presents the PIML-agent, a physics-informed multi-agent strategy for transient voltage support in ultra-high-voltage direct-current (UHVDC) receiving-end systems. A stress-risk signal derived from a reduced-order receiving-end model is fused with local, neighborhood, and receiving-area voltage channels in a distributed control law whose coordination gains are learned by derivative-free policy search over randomized physics-model rollouts. On the IEEE 39-bus benchmark, with all controllers sharing one receiving-end model and identical actuator limits, the PIML-agent reduces the receiving-area voltage deviation integral by 87.67–97.48% relative to no control and 76.95–94.84% relative to local rule-based support across six fault, load, delayed-support, corridor, and UHVDC-recovery scenarios, and its six-scenario mean by 60.05% relative to a cooperative multi-agent controller. It shortens the average sub-0.90 pu violation duration from 3.62 s (local rule) to 0.56 s and restores the voltage above 0.95 pu within 0.80–2.14 s after fault clearing. It outperforms every baseline in all 100 unseen randomized disturbances, and gains transferred without retraining to the 140-bus NPCC system achieve a 94.80% reduction relative to no control. The advantage persists under gain perturbations, communication delay and loss, agent outage, measurement noise, stronger disturbances, reduced capacity, and model mismatch.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Physically informed multi-agent deep reinforcement learning for distributed voltage control in distribution networksInternational Journal of Electrical Power & Energy Systems · 2025
- Physics-Informed Neural Networks for Real-Time Control of Grid-Forming Inverters: Embedding Physical System Laws into Deep Learning ArchitecturesEnergies · 2026
- Multi‐agent deep reinforcement learning‐enabled voltage regulation approach for partitioned active distribution network using heterogeneous PV invertersEnergy Conversion and Economics · 2025
- Reactive Power Optimization for Distribution Networks Based on Parameter-Adaptive Reinforcement LearningEnergies · 2026
- Attention-Enhanced Multi-Agent Deep Reinforcement Learning for Inverter-Based Volt-VAR Control in Active Distribution NetworksMathematics · 2026
- Distribution system Volt-VAR control via transformer-enhanced reinforcement learning with diffusion-driven data augmentationInternational Journal of Electrical Power & Energy Systems · 2026