False Data Injection Screening for Temperature Monitoring of Distribution Transformers Based on Lightweight Blockchain and Winding Structural Fingerprinting
Ying Guan, Sheng Ma, Junqi Yang, Weitao Meng, Bo Zhang, Xingcheng Yu
Key points
From the paper's conclusion- Finite-element simulations and 100-round randomized attack tests show a 9.6% structural temperature deviation that provides a clear physical screening margin: the three attack types are detected and classified within 4 s at a 100% detection rate (95% CI [96.4, 100]%) and a 0.3% false-alarm rate, while a stealthy ramp injection is caught after about 105 min and a sub-threshold constant offset is ca
Abstract
Temperature monitoring underpins the protection and condition assessment of distribution transformers, whose dominant failure mode is overheating-induced insulation aging; this makes temperature data the prime target of false data injection (FDI) attacks. Because FDI acts on data rather than on the physical asset, this paper exploits the winding structure, which data injection cannot alter, as a physical trust anchor: a structural fingerprint is extracted from port measurements through frequency-dependent harmonic resistance; the systematic temperature-response differences between wire-wound and foil-wound windings build an independent physical cross-check channel; and a lightweight PBFT consortium blockchain notarizes the fingerprint baseline so that a compromised local database cannot rewrite it. Structural, physical, and command consistency indicators classify input-, output-, and model-parameter-tampering attacks. Finite-element simulations and 100-round randomized attack tests show a 9.6% structural temperature deviation that provides a clear physical screening margin: the three attack types are detected and classified within 4 s at a 100% detection rate (95% CI [96.4, 100]%) and a 0.3% false-alarm rate, while a stealthy ramp injection is caught after about 105 min and a sub-threshold constant offset is caught by trend monitoring in about 4 h. A seven-node chain implemented with real ECDSA-secp256k1 signatures achieves 0.42–0.90 s finality per notarization, 8.9–19.0 notarizations/s, and a 0.47 s view change, two orders of magnitude above the field notarization demand, meeting lightweight deployment requirements.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Partial discharge fault diagnosis method for metro dry-type transformers based on HHO-BiTCNJournal of Physics: Conference Series · 2026
- An Adaptive Reconstruction and Branch-Interaction Network for False Data Injection Attack Detection in Smart GridsAutomation · 2026
- Toward Intelligent Power Transformer Diagnostics: From Multi-Source Condition Monitoring to Digital TwinsEnergies · 2026
- Dual-Layer Defense: Blockchain-Secured Federated Learning Architecture for Trustworthy Anomaly Detection in IoT-Enabled Smart GridsEnergies · 2026
- A Blockchain-Assisted Ensemble Learning Model for Real-Time Anomaly Detection in Industrial Cyber–Physical SystemsJournal of Cybersecurity and Privacy · 2026
- Topology-Transferable Detection of Deep-Learning False Data Injection Attacks Through Residual-Energy SeparationarXiv · 2026