Automatic Reading of Analog Pointer Meters Based on YOLO Localization and Template-Calibrated Angle-to-Value Mapping
Shijie Zhang, Yu’ang Qin, Hui Zhang, Jilong Wang, Xiang Wu, Zhanyuan Cao, Mengkun Zhang
Key points
From the paper's conclusion- Automatic reading of analog pointer meters is affected by complex backgrounds, illumination changes, and camera viewpoints.
Abstract
Automatic reading of analog pointer meters is affected by complex backgrounds, illumination changes, and camera viewpoints. This study implements and evaluates a template-calibrated reading procedure that integrates established detection and image-processing components for fixed-layout analog instruments with instrument-specific pointer segmentation. YOLO localizes the meter, and the detected region is aligned with a manually calibrated template. Illumination-adaptive color segmentation and geometric processing estimate the pointer angle, which is converted to a reading by interpolation between adjacent calibrated angles. Compared with endpoint-based linear mapping, this procedure uses intermediate scale information to represent local angle–value relationships. Relative to approaches requiring dedicated pointer-segmentation or reading-regression networks, its reading stage avoids pixel-level pointer annotations and dedicated network training, while requiring manual template calibration and suitable pointer-segmentation settings. On the 58-image independent real-scene detection test set, YOLO achieved an mAP@0.5 of 99.50% and an mAP@0.5:0.95 of 77.72%. On 58 still images of a single 0–1.6 MPa pressure gauge, the method achieved a mean absolute error (MAE) of 0.0095 MPa, a root-mean-square error of 0.0135 MPa, and a maximum absolute error of 0.0408 MPa relative to manual reference readings. Image-level predictions were matched to the means of 16 supplied manual readings per image. These errors quantify agreement with those means; the variability and unvalidated uncertainty of the manual references preclude interpreting the MAE as equivalent absolute pressure-measurement accuracy. Supplementary evaluation on 26 images of a second pressure gauge and 28 images of a thermometer yielded scale-normalized MAEs of 0.1870% and 0.0787%, respectively, after instrument-specific calibration and segmentation configuration. These evaluation images informed segmentation-parameter selection; the results therefore illustrate reuse after configuration, without establishing generalization to unseen instruments or images.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- The Study of an Automatic Verification System for Hygrometers Based on Deep LearningEngineering Research Express · 2026
- Automatic reading method of pointer meter based on improved U-Net and scale distance interpolationEngineering Research Express · 2026
- VISIONGAUGE: A COMPUTER VISION MODEL TO DETECT AND READ U-TUBE MANOMETERSArtefactum · 2026
- Vision-Language Models for Analog Gauge Reading: An Empirical Study of Specialization, Transfer and ReliabilityarXiv · 2026
- Mechanism-Constrained Synthetic Data for Detection-Oriented Visual Sensing of Analog Gauges Under Limited Pointer Annotation.Sensors (Basel, Switzerland) · 2026
- Digitization of Analogue Gauges using Computer VisionarXiv · 2026