Optimal Allocation and Sizing of BESS Based on a Reliability-Oriented Planning Approach for Transmission Systems
Sergio David Diaz-Perez, Juan Guillermo Marin-Quintero, Jorge Ivan Silva-Ortega, Rafael Peña Gallardo, Cesar Augusto Orozco-Henao, Andrés Ricardo Herrera-Orozco
Key points
From the paper's conclusion- These results demonstrate the framework’s ability to identify feasible BESS configurations that improve reliability under the adopted modeling assumptions.
Abstract
Planning battery energy storage systems (BESS) in transmission networks requires accounting for the effects of component failures on supply continuity. This paper proposes a reliability-oriented methodology based on a Mixed Gray Wolf Optimizer (MGWO) to determine BESS locations, rated active power capacities, and technology selection between lithium-ion (Li-ion) and vanadium redox flow (VRF) batteries. The framework incorporates stochastic reliability models for transmission lines, transformers, busbars, and BESS units. The objective is to minimize the equally weighted average of annual energy not supplied (ENS) across single-generator-outage scenarios, subject to technical constraints and an investment budget. BESS sizing refers to rated power in MW; energy capacity and chronological state of charge are not explicitly modeled. The methodology is evaluated using the IEEE 39-bus New England test system with representative hourly demand profiles. Under a maximum investment budget of USD 300 million, the selected solution comprises 338.66 MW of installed BESS capacity, including 280.78 MW of Li-ion storage and 57.88 MW of VRF storage, at a total investment of USD 299.87 million. Relative to the reference case, SAIDI and SAIFI decrease by 13.76% and 13.11%, respectively. During optimization, the fitness value decreases from approximately 0.878 to 0.828 p.u., representing an improvement of about 6.5% relative to the initial solution. Ten independent runs yield final fitness values between 0.8213 and 0.8300 p.u. These results demonstrate the framework’s ability to identify feasible BESS configurations that improve reliability under the adopted modeling assumptions.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Design and evaluation of integrated energy systems under component failures for balancing reliability, costs, and greenhouse gas emissionsEnergy Conversion and Management · 2025
- Reliability-oriented optimal planning of photovoltaic distributed generation and energy storage in radial distribution networksResults in Engineering · 2026
- Supporting Data Center Grid Integration via Co-Optimized Battery Energy Storage Sizing and Capacity AllocationarXiv · 2026
- Hybrid algorithm–driven optimal configuration of energy storage systems based on renewable generation forecastingJournal of Renewable and Sustainable Energy · 2026
- Reliability-based Sizing of Energy Storage for Large Load IntegrationarXiv · 2026
- Optimal locations and capacities of multiple BESSs in a RES-integrated distribution network: a real-world case studyScientific Reports · 2026