Edge Computing Architecture for Optimal Settings of Inverse Time Overcurrent Relays in Mesh Microgrids
Gustavo Arteaga, John E. Candelo-Becerra, Jhon Montano, Javier Revelo-Fuelagán, Fredy E. Hoyos
Universidad Nacional de Colombia · Instituto Tecnológico Metropolitano
Key points
From the paper's conclusion- The results of the graph theory show that all the meshes, fault locations, and relay pairs were identified in the MG.
Abstract
This paper presents a novel edge-computing-based architecture for optimal inverse time overcurrent relays installed to protect mesh microgrids (MGs) with distributed generation. The procedure employs graph theory to automate the detection of network changes, fault locations, and relay pairs in an MG. In addition, an automated process obtains the initial protection settings based on the operating conditions of the MG. Furthermore, the Continuous Genetic Algorithm (CGA), Salp Swarm Algorithm (SSA), and Particle Swarm Optimization (PSO) were implemented to determine the optimal protection settings to obtain better coordination between primary and backup protection relays. These processes were implemented using PowerFactory 2024 Service Pack 5A and Python 3.13.1. The proposal was validated in 68 operating scenarios that considered the islanded and connected operation modes of the MG, charging and discharging cycles of electric vehicle stations, and the presence or absence of photovoltaic generation. The overcurrent protection relays were organized into 100 primary–backup relay pairs to ensure proper coordination and selectivity. The total miscoordination time (TMT) index was used to measure when all pairs of relays were coordinated, with a minimum time close to zero. The results of the graph theory show that all the meshes, fault locations, and relay pairs were identified in the MG. The approach successfully coordinated 100 relay pairs across 68 scenarios, demonstrating its scalability in complex real-world MGs. The automation process obtained an average TMT of 12.2%, while the optimization obtained a TMS of 91.6% with the CGA, and a TMT of 99% was obtained with the SSA and PSO, demonstrating the effectiveness of the optimization process in ensuring selectivity and appropriate fault clearing times.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Topology-Driven Global Optimization of Directional Overcurrent Relay Settings in ADNs via Graph-Theoretic Coordination-Pair Generation and MINLP.Journal of visualized experiments : JoVE · 2026
- Integrated Network Reconfiguration and Adaptive Protection Coordination in Active Distribution SystemsApplied Sciences · 2026
- Performance evaluation of advanced metaheuristic algorithms for directional overcurrent relay coordination in distribution networksScientific Reports · 2025
- Topology-Aware Feasibility Assessment and Coordinated Setting of Transformer Primary and Backup Protection in Islanded Renewable Power SystemsEnergies · 2026
- Adaptive Overcurrent Protection of Distribution Substations with Definite-Time CharacteristicsEnergies · 2026
- Voltage sag and short interruption edge-side tracing model based on a spiking spatiotemporal causal graph convolutional networkAIP Advances · 2026