Gilberto Guzman, M. Madrigal, E. Melgoza
This paper presents the implementation of the Grid-Forming (GFM) control technique in renewable energy source inverters to synchronize with the grid and provide frequency support. Specifically, the GFM Droop Control technique, based on the Power–Frequency relationship, is employed. The proposed model was developed and validated in the Matlab-Simulink environment. By using electromagnetic transient (EMT) simulations, we were able to precisely monitor and analyze voltage and current waveforms, thereby confirming the approach’s effectiveness in enhancing grid stability and power quality. The implementation of the GFM control technique in islanded mode demonstrated high system frequency stability. In response to sudden load changes up to 5 MW (equivalent to over 30% of the total load), a maximum frequency deviation of 0.04 Hz and a maximum Rate of Change of Frequency (RoCoF) of 4 Hz/s were observed. The system ensured the frequency’s return to its nominal value of 60 Hz, thanks to the virtual inertia and frequency regulation provided by the GFM. The total harmonic distortion (THD) of current and voltage in steady-state operation consistently remained below 1%, thus complying with IEEE 1547 standards. In tests with the GFM interconnected to the grid, the droop+LPF control provided dynamic support to the external system, effectively mitigating both frequency deviations and RoCoF. The GFM contributes to the grid’s frequency stability by providing virtual inertia. The power quality at the point of common coupling (PCC) was excellent, as the voltage distortion was maintained below 0.5%, confirming that the injection of harmonic currents does not violate established limits.