Thermal Energy Storage and Peak-Demand Reduction in a Retrofitted TABS Office Building: Measured Performance and a Simulation-Based Comparison of Slab Typologies Differing in Composition and Pipe Position
Rossana Laera, Inmaculada Martínez Pérez
Key points
From the paper's conclusion- This study aims (i) to document compliance with the LEED v5 Grid Harmonization credit at Apolonio Morales 29, an office building in Madrid certified in 2025 with the highest score worldwide for this version; and (ii) to compare six slab typologies through adiabatic simulations with fixed operating parameters.
Abstract
Thermally activated building systems (TABS) shift energy demand away from grid peaks, yet retrofitted buildings often retain heterogeneous slabs, unlike the homogeneous slabs assumed in most studies. This study aims (i) to document compliance with the LEED v5 Grid Harmonization credit at Apolonio Morales 29, an office building in Madrid certified in 2025 with the highest score worldwide for this version; and (ii) to compare six slab typologies through adiabatic simulations with fixed operating parameters. Measurements show winter thermal peak-demand reductions of up to 90%, with a median 15 h reduced-demand period on 126 of 129 winter working days; simulated behavior was checked for consistency with these data. Composition mainly determined heat distribution between floors (inter-floor air-temperature gap of 1.5–1.6 °C in heterogeneous versus ≈ 0.7 °C in homogeneous slabs), whereas pipe depth and intervening mass determined accumulated demand (up to +82%). Heterogeneous slabs, like the case study, suit directional heating and a single nightly charging window; homogeneous slabs can serve two floors from one circuit at higher demand. Sensitivity analyses show relative demand and temperature patterns persist when infiltration or supply temperature change, whereas absolute demand and cycle durations do not, supporting relative comparisons for design and control.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Understanding energy flexibility in buildings: A sensitivity analysis of building characteristics and thermal storage potentialEnergy and Buildings · 2026
- Disaggregation of heating energy into domestic hot water and space heating for apartment buildings: A Norwegian case study.Energy and Buildings · 2026
- Comparative evaluation of stratified TES models for digital twin applications using real-world operational dataE3S Web of Conferences · 2026
- Calibrated intra-era archetypes for the Swedish multi-family housing stockE3S Web of Conferences · 2026
- Comparative review of hybrid forecasting models for short-term prediction of building thermal loadarXiv · 2026
- Data-driven analysis of building thermal performance using room-level thermal time constantsE3S Web of Conferences · 2026