Numerical Assessment of an Asymmetric Freezing Pipe Layout for an Irregular Subway Passage Adjacent to Existing Subway and Residential Structures
Peirong Li, Zhaoping Li
Key points
From the paper's conclusion- Compared with a conventional symmetric layout, the maximum ground surface uplift, building foundation displacement, and existing subway structure displacement were reduced by approximately 2.5%, 3.1%, and 8.3%, respectively.
Abstract
Artificial ground freezing (AGF) is widely used for ground reinforcement and groundwater control in urban underground construction, but its application to irregular subway station passages is challenging when the freezing zone is constrained by existing underground structures and nearby buildings. In this study, the planned X-1 passage at Gaojiayuan Station of Beijing Metro Line 14 was adopted as an engineering design scenario. The passage was still at the engineering design stage and had not yet entered construction. An asymmetric freezing pipe layout was proposed to balance frozen wall development and frost heave control under the asymmetric surrounding constraints. Freezing pipes near the existing subway structure were arranged to compensate for the prescribed thermal disturbance, whereas those near the residential buildings were shifted inward to limit unnecessary outward freezing. A three-dimensional sequential thermo-mechanical numerical model was established to evaluate temperature and displacement responses during active freezing. After 60 days, a continuous frozen wall was formed, and the volume-averaged temperature within the designed 2.0 m thick frozen wall domain reached −10.56 °C, below the prescribed limit of −5 °C. Compared with a conventional symmetric layout, the maximum ground surface uplift, building foundation displacement, and existing subway structure displacement were reduced by approximately 2.5%, 3.1%, and 8.3%, respectively. Sensitivity analysis showed that these relative displacement reductions remained stable when the equivalent frost heave coefficients were varied by ±20%. Among the investigated cases, a 200 mm inward offset provided a reasonable comparative balance between frozen wall development and deformation mitigation under the adopted model assumptions. For the investigated design-stage case, the results indicate that a constraint-oriented asymmetric freezing-pipe layout can redistribute the freezing influence while maintaining the prescribed frozen-wall requirements.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Thermal Response of a Frozen Wall to Freezing-Pipe Failure During Underground Shield Docking: A Three-Dimensional Phase-Change Analysis Evaluated Against Field MeasurementsProcesses · 2026
- Heat transfer analysis of thawing behavior in artificially frozen subway cross passage under seepage conditionsTunnelling and Underground Space Technology · 2026
- Numerical Simulation and Machine Learning for Pipeline Settlement Prediction in Urban Metro Station Construction: A Case Study of Shenyang MetroInfrastructures · 2026
- Evaluating the Deformation Performance of Long and Narrow Subway Foundation Pits and Their Effects on Adjacent Buildings: Insights from Numerical Modeling and On-Site MonitoringBuildings · 2026
- Study on the Vibration Isolation Effect of a Collaborative System Composed of Widened Trench and Diaphragm Wall in Foundation Pits on Subway-Induced VibrationssBuildings · 2026
- Evolution of Construction Mechanics Behavior in Widening Section of Urban Highway Tunnel with Super Cross-SectionBuildings · 2026