Monthly Peak-Shaving Control Strategies and Economic Analysis of an Ice-Storage Air-Conditioning System for Metro Stations
Xianggan Zhao, Xiangui Shang, Junjie Jiang, Mingyang Gao, Mingyu Deng, Jing Chen
Key points
From the paper's conclusion- The balanced load-distribution strategy saves 0.49–14.90% of energy compared with full-load operation; the combined cold-storage-priority and peak-shaving strategy reduces the monthly demand charge by 15.69% and the annual electricity cost by 2.32% versus the single cold-storage-priority strategy; the ice-storage scheme cuts the annual energy cost by 23.02% versus the conventional system, with pea
Abstract
The energy consumption and electricity cost of air-conditioning systems in metro stations keep rising with the expansion of rail transit. Ice thermal-energy storage (ITES) shifts cooling load to off-peak hours, yet existing studies mostly optimize ice-storage operation on a daily scale and rarely address multi-chiller load distribution, the coordination of the large and small systems of a station, or monthly peak shaving adapted to the two-part electricity tariff. For a standard metro station with platform screen doors in Wuxi, China, the annual hourly cooling loads of the large and small systems are simulated with DeST 2.0, and energy-consumption models of the chillers, multi-split units, and pumps are established. A two-layer monthly peak-shaving framework is then proposed: for the large system, a balanced load-distribution strategy and three stored-cooling allocation schemes (base-load chiller priority, cold-storage priority, and peak shaving) integrated via a monthly load-baseline switching model; for the small system, three annual regulation strategies. The balanced load-distribution strategy saves 0.49–14.90% of energy compared with full-load operation; the combined cold-storage-priority and peak-shaving strategy reduces the monthly demand charge by 15.69% and the annual electricity cost by 2.32% versus the single cold-storage-priority strategy; the ice-storage scheme cuts the annual energy cost by 23.02% versus the conventional system, with peak-shifting and valley-utilization ratios of 56.89% and 39.75%; and the energy-efficiency-priority strategy lowers the small-system energy consumption, operating cost and carbon emission by 8.19% and 16.90%. As these strategies are derived from the load profile and tariff structure of the case station, their applicability to stations with different conditions requires further validation.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Innovative combination of optimization and energy management strategies for integrated cooling, heating and power systems with ice thermal energy storageJournal of Energy Storage · 2026
- Holding the Cold: Retention-Aware Inventory Control for Industrial RefrigerationarXiv · 2026
- Investigation on Electricity Flexibility and Demand-Response Strategies for Grid-Interactive BuildingsBuildings · 2025
- Peak reduction via time-variable tariffs and automated load control: Results from a Swiss pilot studyApplied Energy · 2026
- Data-Driven Offline Reinforcement Learning for Adaptive Flow-Rate Control of Phase Change Material Thermal Storage SystemsE3S Web of Conferences · 2026
- Building Seasonal Highways for Residential Energy Hubs: Sizing, planning and operating thermal energy storagearXiv · 2026