From the paper's conclusion- The results indicate that the IJV location influences airflow and temperature distributions more strongly than the diffuser geometry.
Abstract
Impinging jet ventilation (IJV) systems have attracted significant attention due to their potential to augment indoor thermal comfort and airflow distribution. Previous studies have primarily investigated corner and mid-wall IJV installations; however, comparative analyses focusing on different diffuser geometries remain limited. Accordingly, this study examines the combined effects of IJV diffuser geometry and installation location on thermal comfort indices and airflow characteristics. A full three-dimensional computational fluid dynamics (CFD) model, without the use of symmetry, is developed to simulate a realistic office environment (3 × 3 × 2.9 m3), operating in cooling mode under hot summer climatic conditions. Three IJV diffuser cross-section geometries—triangular, square, and circular—are evaluated at four installation locations (two corners and two mid-wall positions), assuming a fixed occupant location. A combined return and exhaust outlet configuration is adopted. The results indicate that the IJV location influences airflow and temperature distributions more strongly than the diffuser geometry. Nevertheless, the circular diffuser exhibits superior performance compared to the triangular and square geometries. The mid-wall location placed behind the occupant and away from the hot exterior wall demonstrates reduced thermal stratification, improved airflow characteristics, and weaker vortex formation, making it the most favorable configuration. From an architectural perspective, these findings highlight the importance of early coordination between ventilation design and office spatial planning, as diffuser placement directly influences occupant comfort zones and furniture layout. Moreover, the preference for mid-wall installations supports a more flexible façade design and allows for greater freedom in organizing workspaces without compromising thermal performance.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Experimental study on the influence of supply terminal shape on temperature, contaminant distributions and flow characteristics in impinging jet ventilationBuilding and Environment · 2026
- Parameter trade-off in impinging jet ventilation for optimal thermal comfort of metro carriagesPhysics of Fluids · 2026
- Toward an accurate CFD modeling of a realistic supply ventilation terminal: Sensitivity analysis of computational and physical parametersBuilding and Environment · 2026
- HEAT TRANSFER AND CONVECTION ANALYSIS FOR THERMAL COMFORT OPTIMIZATION IN AN OFFICE WITH GLASS PARTITION ZONINGRevista Foco · 2026
- Two-phase flow dynamics of gas jet impingement under reduced boundary layer effectsPhysics of Fluids · 2026
- Mixing ventilation by in-seat air outlets for single-aisle aircraftCEAS Aeronautical Journal · 2026