TSO Digital Control Room with Human-in-the-Loop for Enhanced Grid Operation with SMR Integrations
Hossam A. Gabbar, Nathanael Selvaraj, Jake Bastin
Key points
From the paper's conclusion- With the retrospective SMR human performance analysis based on the implementation of the defined HPMS/HPSN method, the average heuristic error-risk index value was raised from 0.353 during the baseline period to 0.411 during the trip and diagnosis, and the average value of the HPMS performance ratio was reduced from 4.331 to 3.472.
Abstract
This paper describes a human-in-the-loop TSO-DCR architecture that incorporates transmission system simulation, HMS, HPMS, and HPSN. MATLAB App Designer, MATPOWER, and Simulink/Simscape Electrical were used to examine baseline conditions, a transmission disturbance due to a weather event, and an 85 MW SMR generation trip. In the weather disturbance scenario, the outage of Line 7–8 resulted in an increase in the loading of Line 8–9 to 117.6%, while the minimum bus voltage was reduced to 0.969 p.u. Further corrective measures were taken that decreased the loading of the chosen branch to about 96.0% while increasing the minimum bus voltage to 0.987 p.u. The SMR generation-trip event produced a simulated minimum frequency of 59.589 Hz and was followed by the activation of the replacement reserves and the return of the frequency to its normal level. With the retrospective SMR human performance analysis based on the implementation of the defined HPMS/HPSN method, the average heuristic error-risk index value was raised from 0.353 during the baseline period to 0.411 during the trip and diagnosis, and the average value of the HPMS performance ratio was reduced from 4.331 to 3.472.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Integrated digital control room with human-in-the-loop for effective SMR operationNuclear Engineering and Design · 2026
- An Explainable Cyber Range-to-MATLAB Co-Simulation Framework for Attack-Chain and Power-Service Impact Analysis in Electric Power NetworksElectronics · 2026
- Design and Implementation of a Human Machine Interface for Online Cable Condition MonitoringApplied Sciences · 2026
- AI Agents Executing an RMS and EMT Ride-Through Workflow on a 2,000-Bus Synthetic Texas Grid: A Case Study with Open-Source ToolsarXiv · 2026
- GRID-MRI: Resilience Assessment of Power Systems under Coordinated Cyber-Physical AttacksarXiv · 2026
- Analysis of the Impact of Distributed Generation on the Frequency Stability and Rotational Inertia of the Electric SystemElectronics · 2026