The Effect of Conductor Geometry on Electric Field Distribution in Air-Insulated Medium Voltage Busbar Systems
Ahmet Can Yalcin, Huseyin Akdemir, Cihat Cagdas Uydur, Bekir Dursun
Key points
From the paper's conclusion- The findings indicate that profile geometry serves as an effective design measure in mitigating electrical stress and reducing partial discharge risk in medium-voltage equipment.
Abstract
In the design processes of medium-voltage (MV) systems, ensuring insulation safety is considered a critical parameter in terms of both system sustainability and the service life of the components used. In this study, the direct effects of the cross-sectional geometry of conductors used in air-insulated switchgear (AIS) systems on electric field distribution and dielectric strength characteristics were quantitatively investigated through numerical analysis methods. Within the scope of the research, conductor models with different geometric structures were created based on a rated line-to-line voltage level of 17.5 kV, and these models were analyzed using the finite element method with COMSOL Multiphysics® (AC/DC Module 6.2 version) software under the rated peak inter-phase potential difference (24.75 kV). Simulation studies demonstrate that curved transitions at the rounded edges on conductor surfaces cause electric field lines to concentrate at these boundaries, leading to local electric field intensification. In calculations performed on a standard rectangular cross-section conductor with dimensions CU-6 × 180 mm, the maximum electric field strength reached 10.90 kV/cm at the rounded edges. For wider rectangular profiles such as CU-12 × 220 mm and CU-12 × 360 mm, maximum field strengths remained at 7.77 kV/cm and 7.42 kV/cm, respectively. In contrast, adopting equal-area cylindrical configurations for these profiles reduced the peak electric field to 4.54 kV/cm (for the 12 × 220 mm equivalent) and 4.22 kV/cm (for the 12 × 360 mm equivalent) owing to the uniform charge distribution across the continuous cylindrical boundary. Beyond the qualitative understanding of electrostatic curvature, this study quantitatively benchmarks the dielectric safety margins and field utilization factors for standardized industrial MV busbar profiles at 17.5 kV, providing practical geometric criteria for partial discharge mitigation in compact switchgear designs. The findings indicate that profile geometry serves as an effective design measure in mitigating electrical stress and reducing partial discharge risk in medium-voltage equipment.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Integrated Insulation Coordination for Pollution- and Lightning-Exposed Medium-Voltage Distribution NetworksEng · 2026
- Thermal regulation mechanism of embedded heat-pipe-assisted conductors under high heat-flux electrical loadingInternational Journal of Thermal Sciences · 2026
- Bypass Sheath Voltage Limiters at Cable-to-GIS Terminations: Geometry-Resolved Connection-Lead Impedance for Insulation Coordination Under Very Fast Transient OvervoltagesEnergies · 2026
- Full-process evaluation of lightning protection for multi-circuit 10 kV distribution linesJournal of Physics: Conference Series · 2026
- Influence of semiconductive shielding protrusions on the electric field distribution in ±500 kV HVDC cables.PloS one · 2026
- Parametric Vibration Characteristics of Composite Suspension Insulator Strings Under Axial Dynamic LoadsApplied Sciences · 2026