Nonlinear Model Predictive Control of Process Water Quality in the Closed-Loop Water Circuit of the Aktogai GOK Flotation Plant
Laulasyn Abzhanova, Akerke Absatarova, Svetlana Khan, Gulmira Iskakova, Larissa Rudakova, Laura Sugurova
Key points
From the paper's conclusion- It persisted under up to 30% adverse parametric plant–model mismatch, and the results were insensitive to tenfold variations in the selected NMPC tuning weights.
Abstract
This paper presents a simulation-based feasibility study of nonlinear model predictive control (NMPC) for process water quality management in the closed-loop water circuit of the Aktogai copper concentrator. Repeated water recirculation leads to the accumulation of total dissolved solids (TDSs), organic compounds (CODs), and suspended solids (TSSs), degrading flotation efficiency. A dynamic model of the process water pond with nine flows is combined with pseudo-first-order kinetics for H2O2 oxidation (kox = 0.003 L/(mg·h)) and polyaluminum chloride (PAC)/FeCl3 coagulation (kcoag = 0.005 L/(mg·h)). The NMPC manipulates the treated-effluent flow Q2 and the coagulant and oxidant doses over an 8 h prediction horizon, uses normalized one-sided soft constraints on water quality and a reagent cost, and is solved through sequential quadratic programming. The volume, TDSs, and TSSs are assumed to be measured online, whereas CODs are available only from laboratory analyses taken every 2–8 h with a 2 h delay. NMPC was compared with no-control, fixed dosing, a maximum-dilution policy, and a proportional–integral (PI) feedback dosing benchmark with the same manipulated variables. Under nominal disturbances, all strategies met the process limits. Under a simulated stress-test scenario (ore change and reagent overdosing), no control produced 26, 37, and 25 h of TDS, COD, and TSS violations in 72 h; maximum dilution alone removed the TDS and TSS violations but left 13 h of COD violations. With online measurements, a well-tuned PI controller performed almost as well as NMPC (1 h vs. 0 h of COD violations). With laboratory COD analyses, the PI controller incurred 4–11 h of COD violations, whereas NMPC, using a model-based COD estimate between analyses, incurred none, at the cost of 9–47% higher oxidant consumption; this advantage reflects the combined effect of model-based COD estimation and predictive optimization, not of predictive optimization alone. It persisted under up to 30% adverse parametric plant–model mismatch, and the results were insensitive to tenfold variations in the selected NMPC tuning weights. TDSs could be held below their limit only through hydraulic dilution and only while the thickener-overflow TDSs remained below about 2260 mg/L.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- AI-enabled CPS operational framework with daily-retrained model bank for chemical resource optimization in drinking-water treatment.Journal of environmental management · 2026
- Model-Predictive Control for Constrained Wastewater Treatment Processes With Stochastic Sampling IntervalsIEEE Transactions on Cybernetics · 2026
- Research on GLCC liquid level-pressure control method based on NMPC with channel-decoupled multi-residual consistency monitoringEngineering Research Express · 2026
- Threshold-driven reuse of mineral processing water: selective treatment and AI-ready monitoring for fit-for-purpose control.Water research · 2026
- Convex, Real-Time Koopman Model Predictive Control of Activated-Sludge Aeration: Constraint-Aware Operation With an Explicit Energy-Nitrous-Oxide Operating Frontier.Water environment research : a research publication of the Water Environment Federation · 2026
- Development of a Method for Supervising Air and Reagent Flow Control During Copper-Sulfide Ore FlotationEng · 2026