A Binary Hybrid Particle Whale Optimization Framework for Feature Selection in Industrial Transformer Partial Discharge Classification
Lucas Thobejane, Bonginkosi Thango
Key points
From the paper's conclusion- This study proposes a binary hybrid particle whale optimization algorithm (BHPWOA) for multi-objective wrapper-based feature selection in transformer insulation severity classification.
Abstract
Partial discharge (PD) testing based on IEC 60270 is widely employed for assessing the insulation integrity of power transformers. Although numerous statistical descriptors can be extracted from PD measurements, redundant and irrelevant features can degrade classification performance, particularly in small datasets. This study proposes a binary hybrid particle whale optimization algorithm (BHPWOA) for multi-objective wrapper-based feature selection in transformer insulation severity classification. The analysis comprises 64 IEC 60270 partial-discharge test sessions collected from 30 power transformers. Seventeen candidate statistical, temporal, spectral, derived, and test-configuration features were evaluated; the transformer identifier (TransClass) was excluded before wrapper optimization because it would not be available for an unseen transformer. Candidate subsets were assessed with a k-nearest neighbors (KNN) classifier using five-fold StratifiedGroupKFold cross-validation grouped by TransformerID, with min–max scaling fitted exclusively within each training fold. BWOA and BSFSA achieved the best multi-objective fitness (−0.9227) with the two-feature subset {CV_PD, Exc100}, corresponding to an 88.2% reduction, 93.75% accuracy, and macro-F1 of 0.9313. BHPWOA selected five features {MeanPD, CV_PD, Exc100, Q95_PD, MeanPD_Early}, corresponding to a 70.6% reduction, 92.19% accuracy, and macro-F1 of 0.9163. Across five BHPWOA stability runs, the mean feature count was 4.6 +/− 1.02, mean accuracy was 0.909 +/− 0.021, and mean macro-F1 was 0.903 +/− 0.022; CV_PD and Exc100 were selected in all five runs. Because the same grouped partition is used for wrapper selection and reported out-of-fold performance, these values are internal, non-nested grouped-CV estimates rather than independent outer-CV estimates.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Leakage-Controlled Multi-View Probability Fusion for DGA-Based Power Transformer Fault Classification: Optimization Ablation and Robustness AnalysisMachines · 2026
- Research on the dimension reduction of the partial discharge feature space for oil-paper insulated power transformerScientific Reports · 2026
- Machine Learning for Early Transformer Insulation Defect Risk RankingEnergies · 2026
- A Hybrid Optimization Model for Transformer Fault Diagnosis Based on Gas ClassificationDigital · 2026
- Physics-Guided Dual-Domain Transformer for Reliable Partial Discharge Recognition of Power Cable Insulation under Heterogeneous Acquisition ConditionsEngineering Research Express · 2026
- PCA and Autoencoder-Based ANN Models for Transformer Fault Diagnosis Using Dissolved Gas Analysis: Comparative Insights and ChallengesEnergies · 2026