Agriculture

PSO–Fuzzy–PID Control with Static Psychrometric Decoupling for Modular Plant Factory Environment

Bin Zhang, Fuxi Shi, Zenglin Zhang, Sigao Li, Ziming Liu

Key points

From the paper's conclusion
  • The edge-first programmable logic controller (PLC) architecture, combined with cloud telemetry and static decoupling, offers a practical, scalable solution for intelligent environmental control in modular plant factories with artificial lighting (PFALs), bridging the simulation-to-reality (Sim-to-Real) gap identified in recent reviews.

Abstract

Temperature and humidity control in modular edible fungi plant factories is challenging because of strong bidirectional coupling and mismatched loop dynamics: the pure delay is 1779 s in the temperature channel and 1462 s in the humidity channel. To address this, we developed a control framework that combines a particle swarm optimization (PSO)-based fuzzy proportional-integral-derivative (Fuzzy–PID) feedback controller with static psychrometric decoupling. The static compensation cancels steady-state cross-channel coupling, while the Fuzzy–PID feedback loop handles transient interactions. The system model integrates mechanistic energy/mass balance analysis with random forest regression (coefficient of determination R2 = 0.934 for temperature and 0.927 for humidity), and step-response experiments yield first-order-plus-dead-time (FOPDT) transfer functions. A fourth-order polynomial fit to the Magnus–Tetens psychrometric relation provides the static decoupling. Using an integral of time-weighted absolute error (ITAE) criterion, PSO tunes the initial PID gains (proportional Kp, integral Ki, derivative Kd) for both loops in a six-dimensional search. Physical validation in a 21 m2 oyster mushroom chamber over 23 h achieves ±0.3 °C and ±2.3% relative humidity (RH) maximum deviation from setpoint. In a 1 h comparative test, the PSO–Fuzzy–PID reduced the temperature rise time from 34 min to 17 min and the humidity rise time from 40 min to 20 min, corresponding to a 50.0% reduction in both cases relative to conventional PID. Real-time telemetry completeness reached 99.2% at 1 min intervals, while the 23 h stability record at 1 h intervals achieved 95.8% completeness. This field demonstration validates the strategy in a single chamber during oyster mushroom fruiting; other species or growth stages require re-validation. The edge-first programmable logic controller (PLC) architecture, combined with cloud telemetry and static decoupling, offers a practical, scalable solution for intelligent environmental control in modular plant factories with artificial lighting (PFALs), bridging the simulation-to-reality (Sim-to-Real) gap identified in recent reviews.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers