Siting and sizing of converter interfaced distributed energy resources in medium voltage networks, ensuring small signal stability
Georgia Saridaki, Nikos Hatziargyriou, Aris Dimeas, Xi Luo, Efstratios Batzelis
Key points
From the paper's conclusion- The increasing penetration of converter interfaced Distributed Energy Resources (DER) poses new challenges to the planning and operation of power systems, as they have inherently different characteristics than traditional synchronous machines.
Abstract
The increasing penetration of converter interfaced Distributed Energy Resources (DER) poses new challenges to the planning and operation of power systems, as they have inherently different characteristics than traditional synchronous machines. Considering the hosting saturation of current MV networks observed in many countries, one of the critical planning decisions is the critical distance from the MV bus, that DER can be connected without causing stability problems. This is also affected by their size and their control parameters. In this work, a framework for determining the stability boundary of the distribution line length for specified DER characteristics and determining appropriate DER capacity/control parameters for an existing connection is presented and validated in time domain simulations. The critical modes for single and multiple inverters connected at MV lines and operating in either Grid-following (GFL) or Grid-forming (GFM) mode are calculated. The critical length for the MV voltage line of a single GFL inverter is calculated and compared to multi-inverter scenario. A sensitivity analysis of the different Phase-locked loop (PLL) bandwidths, grid strength and active power setpoints is conducted to investigate their influence on the critical length of the MV line. The impact of switching, the operating mode of the inverter from GFL to GFM in the single and multi-inverter scenario is also investigated.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy FunctionarXiv · 2026
- Small-signal stability analysis of grid-forming and grid-following inverters in islanded microgridsInternational Journal of Emerging Electric Power Systems · 2026
- Architectural Vulnerability Mapping and Analysis in Hybrid AC/DC Distribution NetworksEnergies · 2026
- Advanced control and protection strategies for grid-forming inverters in microgrids—A reviewInternational Journal of Electrical Power & Energy Systems · 2025
- Capacity Ratio Estimation and Capability Assessment for Hybrid Grid-Following and Grid-Forming Converter SystemsEnergies · 2026
- Advancing Hybrid AC/DC Microgrid Converters: Modeling, Control Strategies, and Fault Behavior AnalysisEnergies · 2025