Integral sliding-mode current regulation for sequence-impedance shaping and oscillation suppression in virtual synchronous generators
Lihong Ma, Zhongzhong Li, Jianhua Yin, Haisheng Wang, Sifan Li, Changjun Zhang, Lanqing Lin
Key points
From the paper's conclusion- The results indicate that the proposed integral sliding-mode current regulation improves the operational reliability of grid-forming BESS under the tested grid conditions, thereby supporting power system resilience.
Abstract
Cascade-controlled virtual synchronous generators (VSGs), widely adopted in grid-forming battery energy storage systems (BESS), may experience low-frequency instability when connected to stiff grids characterized by relatively high short-circuit ratios (SCRs) and small equivalent grid impedances. A frequency-coupled sequence-impedance model was developed to investigate the instability mechanism. The conventional proportional-integral (PI) current regulator was replaced with an integral sliding-mode controller incorporating an integral sliding surface and a boundary-layer reaching law, while retaining the outer power and voltage control loops. Small-signal impedance analysis, MATLAB/Simulink simulations, and RT-LAB real-time simulation tests were conducted under different SCR conditions. The baseline model identified a capacitive region in the positive-sequence impedance that resulted in insufficient phase margins at converter-grid impedance crossovers. The proposed controller narrowed the capacitive region and yielded positive phase margins in the analyzed cases. Simulations and real-time tests confirmed the suppression of sustained grid-current oscillations. Compared with a fixed virtual-inductance benchmark, the proposed method shortened recovery time and reduced grid-current total harmonic distortion from 3.38% to 0.54% at SCR = 30 (Lg = 1.5 mH). The results indicate that the proposed integral sliding-mode current regulation improves the operational reliability of grid-forming BESS under the tested grid conditions, thereby supporting power system resilience. These conclusions are limited to the examined balanced three-phase operating conditions and do not establish a universal stability boundary.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Transient Synchronizing Stability Analysis of VSG Considering Voltage/Current Source Mode Switch Induced by Current Saturation LimitProcesses · 2026
- Enhanced Grid-Forming Operation of Virtual Synchronous Generator UnitsIEEE Transactions on Power Delivery · 2025
- A Hybrid Power Synchronization Scheme for Stability Enhancement of Virtual Synchronous Generator ControlIEEE Transactions on Power Electronics · 2025
- Multi-objective integrated VSG control strategy under unbalanced conditionsCircuit World · 2026
- Modeling, Control, and Impedance Analysis of Grid-Forming BESS with NPC TopologyEnergies · 2026
- Robust Full-State Feedback Power Decoupling Control for Grid-Forming Converters Under Line-Impedance MismatchApplied Sciences · 2026