Infrastructure-reuse electrical monitoring using Node-RED and modbus TCP: a 30-day operational evaluation of an industrial three-phase motor

Wilmer Benjamín Vargas Chacón, Karen Esteincin Cuba Vargas, Carlos Alberto Olivera Ylla

Key points

From the paper's conclusion
  • The findings demonstrate the operational feasibility of the proposed architecture under the evaluated conditions.

Abstract

Introduction Many industrial facilities possess electrical measurement equipment but lack accessible tools for acquiring, storing, and visualizing the data generated by these devices. This study aimed to design, implement, and operationally evaluate an Internet of Things (IoT) architecture that reuses existing industrial measurement infrastructure through Node-RED and Modbus TCP. Methods An existing Allen-Bradley PowerMonitor 500 was integrated with Node-RED through Modbus TCP to acquire L1–L2 voltage, L1 current, L1 active power, L1 power factor, and frequency at 2-min intervals during two scheduled daily monitoring periods. The evaluation covered 30 effective monitoring days and 240 scheduled operating hours. Data completeness and descriptive electrical statistics were assessed after screening the dataset using predefined technical thresholds. Results All 7,200 expected records were generated, corresponding to an acquisition completeness of 100%. Six records contained isolated values outside the predefined thresholds, including current and voltage readings approximately ten times higher than their respective means and frequency deviations of approximately 9 Hz. These anomalies were considered consistent with possible decoding errors but were not independently verified. After excluding these records without imputation, 7,194 valid observations (99.917%) remained for descriptive analysis. Mean L1 active power was 5.25 kW (coefficient of variation: 2.64%), while mean L1 current was 18.96 A (coefficient of variation: 2.92%). Mean L1–L2 voltage and frequency were 220.03 V and 59.9995 Hz, respectively. The mean L1 power factor was 0.7213, representing a 19.86% difference below the reference value of 0.90 used exclusively for descriptive comparison. Discussion Reusing installed industrial equipment and open-source software enabled periodic electrical data acquisition, local CSV storage, and remote visualization without introducing additional measurement hardware. The findings demonstrate the operational feasibility of the proposed architecture under the evaluated conditions. However, they do not establish metrological accuracy, communication availability, energy savings, or economic superiority, as these aspects were not independently assessed.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers