Large-signal stability analysis of reduced-order droop-controlled grid-forming inverters in islanded microgrids
Vishal Verma, Mehdi Jabbari Zideh, Sarika Khushalani Solanki, Jignesh Solanki
Key points
From the paper's conclusion- The reduced model preserves the stability features needed for computationally efficient large-signal analysis and provides practical guidance for filter-bandwidth selection and virtual-impedance design in islanded microgrids.
Abstract
Islanded inverter-dominated microgrids are vulnerable to large disturbances because power-electronic resources provide little inherent inertia. This study develops a tractable nonlinear model for assessing transient angle stability of parallel droop-controlled grid-forming inverters. A five-state nonlinear model of a two-bus microgrid is reduced to three states using a fixed-reference-bus approximation. Equilibrium consistency, linearized dominant modes, and transient trajectories are compared with the full-order model. A Lyapunov candidate is constructed to characterize the region of attraction, and phase portraits and fault simulations are used to evaluate power-measurement filter bandwidth and line resistance-to-reactance ratio. The reduced model reproduces the full-order equilibrium with voltage errors below 0.8 % and frequency errors below 0.07 %, while transient trajectory errors remain below approximately 3.2 %. Low filter cutoff frequencies increase the initial angle-deviation rate and values near 0.5 Hz lead to loss of synchronism. Increasing the line resistance-to-reactance ratio reduces synchronizing strength; trajectories diverge at ratios near 5.1, and post-fault recovery is lost at higher ratios. Additional simulations under varying loading conditions, droop gains, and static virtual impedance demonstrate good reduced-model accuracy under strong-reference conditions. The reduced model preserves the stability features needed for computationally efficient large-signal analysis and provides practical guidance for filter-bandwidth selection and virtual-impedance design in islanded microgrids.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Small-signal stability analysis of grid-forming and grid-following inverters in islanded microgridsInternational Journal of Emerging Electric Power Systems · 2026
- Equivalent virtual inertia modeling and time-constant analysis for multi-generator DC microgridsJournal of Renewable and Sustainable Energy · 2026
- Coordinated Adaptive Inertia–Droop Control for Islanded Renewable Microgrids Under Uncertainty and DelayEnergies · 2026
- Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected InvertersarXiv · 2026
- Optimized droop control-based load flow analysis for islanded AC microgrids with electric vehicle integrationScientific Reports · 2026
- Advanced control and protection strategies for grid-forming inverters in microgrids—A reviewInternational Journal of Electrical Power & Energy Systems · 2025