Local connection vulnerability in a field-modified steel truss box system despite retained global eigenvalue buckling reserve: a finite element case study

Willy Susanto, Sujiati Jepriani, Azizah Istighozah, Taris Z. Masulili

Key points

From the paper's conclusion
  • The results demonstrate that a satisfactory global frame response and substantial elastic buckling reserve do not necessarily ensure adequate local connection performance after field modification.

Abstract

This study presents a mechanics-based global–local finite element assessment of a field-modified steel truss-box (STB) system in which an originally specified solid wide-flange (WF) column was replaced during construction by a built-up assembly comprising wide-flange tee (WT) and angle (L) sections. The modification changed the local force-transfer path at the beam–column–bracing connection. Although the original project-level analysis indicated satisfactory serviceability and ultimate limit-state performance, the altered configuration required further examination of global stability, local stress concentration, and connection-level yielding. A two-stage finite element analysis was conducted using Strand7. The global model used beam elements to evaluate the overall response of the modified STB system, whereas a detailed plate-element submodel was developed for the critical WF–WT connection. The assessment considered the reference loading condition and a representative additional 10 kN bracing-related perturbation load to investigate the sensitivity of the modified connection to changes in load transfer. The study is limited to a numerical case study and does not include direct experimental validation, detailed bolt pretension and slip modelling, residual stresses, geometric imperfections, or nonlinear fracture simulation. The global analysis showed that the modified system retained an elastic eigenvalue buckling reserve, with a global buckling factor of approximately 16.8. However, the maximum global von Mises stress reached approximately $$1.16f_y$$ at the evaluated ULS deformation, indicating that the response was governed by strength demand rather than global elastic buckling. At the connection level, the WT flange developed maximum von Mises stresses of 469.97 MPa under the reference condition and 483.29 MPa after the bracing-related perturbation, corresponding to approximately $$1.88f_y$$ and $$1.93f_y$$ , respectively. The calculated local shear stresses also exceeded the von Mises pure-shear yield threshold, $$f_y/\sqrt{3}$$ . In contrast, the local eigenvalue buckling factor remained above 3.0 for all evaluated cases, indicating that local yielding, rather than local plate buckling, governed the predicted response within the adopted modelling assumptions. The progressive yielding sequence showed that yielding initiated in the WT flange before extending to the WF end plate, identifying the WT flange as the capacity-controlling component of the evaluated connection. The results demonstrate that a satisfactory global frame response and substantial elastic buckling reserve do not necessarily ensure adequate local connection performance after field modification. The proposed global–local framework provides a transferable mechanics-based approach for identifying vulnerable force-transfer regions and supporting the assessment of similar field-modified steel connections.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Local connection vulnerability in a field-modified steel truss box system despite retained global eigenvalue buckling reserve: a finite element case study — Science Skim