An Exploratory Comparison of Indoor Air Quality and Culturable Airborne Microbial Concentrations Among Hospital Waiting Areas With Different Ventilation Conditions in Northern Thailand.

Pantitcha Thanatrakolsri, Natnicha Tammawong, Sasiticha Arworn, Supawinee Srikam, Katiya Ivanovitch, Saowanee Norkeaw

Faculty of Public Health, Thammasat University, Lampang, Thailand. · Faculty of Public Health, Thammasat University, Pathumthani, Thailand.

Key points

From the paper's conclusion
  • These findings demonstrate substantial room-specific heterogeneity in IAQ and provide a site-specific baseline for future multi-site studies and targeted ventilation, filtration, and IAQ management strategies in hospital waiting areas.

Abstract

Few studies have simultaneously characterized physical, chemical, and culturable biological indoor air quality (IAQ) in hospital waiting areas, particularly in tropical healthcare settings. This exploratory observational environmental monitoring study assessed PM2.5, PM10, CO2, CO, thermal environmental parameters, and culturable airborne bacterial and fungal concentrations in five hospital waiting areas with different ventilation conditions in Northern Thailand. Measurements were conducted over nine sampling days and summarized at the room-day level to account for repeated spatial measurements. Significant overall differences among waiting areas were observed for PM10 (p = 0.0012), temperature (p = 0.0006), culturable bacteria (p = 0.0050), and culturable fungi (p = 0.0007), whereas PM2.5, relative humidity, CO, and CO2 did not differ significantly at p < 0.01. No pairwise comparison remained significant after Holm adjustment. Descriptively, Room E, the only mechanically ventilated waiting area, generally showed lower PM10 and culturable bioaerosol concentrations than several naturally ventilated waiting areas; however, these differences cannot be attributed exclusively to ventilation condition because mechanical ventilation was represented by only one room. Neither mixed-effects models (bacteria: p = 0.062; fungi: p = 0.153) nor room/day fixed-effects sensitivity analyses (bacteria: p = 0.542; fungi: p = 0.447) showed significant associations between PM10 and culturable bacterial or fungal concentrations. These findings demonstrate substantial room-specific heterogeneity in IAQ and provide a site-specific baseline for future multi-site studies and targeted ventilation, filtration, and IAQ management strategies in hospital waiting areas.

Read the paper