International Journal of Intelligent Systems

Modelling of Switching Operation Process and Real‐Time Violation Detection Method Based on Dynamic Graph Transformer

Zhi-Qiang Lin, Jing Yan, Jing-He Wen, Haowei Chen, Yong-Liang Feng, Haozhao Lin

Key points

From the paper's conclusion
  • Experiments on 6842 tickets from 12 real substations achieve F 1 = 87.4% (+2.0% over the best 2025 SOTA baseline), 0.6‐step detection latency, 18.3‐ms single‐step inference, 91.2% top‐3 step localisation and only 3.6% F1 drop on three unseen substations.

Abstract

Substation switching operation is a high‐risk manual procedure where any misordering or omission may cause serious safety accidents. Existing rule engines cannot cover the diverse violation patterns induced by topology switching, and sequence‐based deep models ignore electrical topology constraints and the ticket‐level operation task. This paper proposes a real‐time detection method that models the switching‐operation process as a dynamic heterogeneous graph and encodes it with a spatiotemporal dual‐channel dynamic graph Transformer. Each step triggers an incremental hard‐update of graph topology, producing snapshots enriched with device state, electrical polarity, voltage level and topological position; the spatial graph‐attention channel and the temporal causal Transformer channel are jointly conditioned on the operation‐task label. A contrastive strategy mixing controlled violation injection with real held‐out violations alleviates label scarcity; a task‐conditioned multiprototype scorer captures the multimodal distribution of normal operations; a three‐level risk‐graded thresholding scheme aligns alarms with safety‐consequence severity; and a ticket‐level task‐consistency check catches violations where all steps are locally correct but the ticket does not match the declared task. Experiments on 6842 tickets from 12 real substations achieve F 1 = 87.4% (+2.0% over the best 2025 SOTA baseline), 0.6‐step detection latency, 18.3‐ms single‐step inference, 91.2% top‐3 step localisation and only 3.6% F1 drop on three unseen substations.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers

Modelling of Switching Operation Process and Real‐Time Violation Detection Method Based on Dynamic Graph Transformer — Science Skim