Modelling of Switching Operation Process and Real‐Time Violation Detection Method Based on Dynamic Graph Transformer
Zhi-Qiang Lin, Jing Yan, Jing-He Wen, Haowei Chen, Yong-Liang Feng, Haozhao Lin
Key points
From the paper's conclusion- Experiments on 6842 tickets from 12 real substations achieve F 1 = 87.4% (+2.0% over the best 2025 SOTA baseline), 0.6‐step detection latency, 18.3‐ms single‐step inference, 91.2% top‐3 step localisation and only 3.6% F1 drop on three unseen substations.
Abstract
Substation switching operation is a high‐risk manual procedure where any misordering or omission may cause serious safety accidents. Existing rule engines cannot cover the diverse violation patterns induced by topology switching, and sequence‐based deep models ignore electrical topology constraints and the ticket‐level operation task. This paper proposes a real‐time detection method that models the switching‐operation process as a dynamic heterogeneous graph and encodes it with a spatiotemporal dual‐channel dynamic graph Transformer. Each step triggers an incremental hard‐update of graph topology, producing snapshots enriched with device state, electrical polarity, voltage level and topological position; the spatial graph‐attention channel and the temporal causal Transformer channel are jointly conditioned on the operation‐task label. A contrastive strategy mixing controlled violation injection with real held‐out violations alleviates label scarcity; a task‐conditioned multiprototype scorer captures the multimodal distribution of normal operations; a three‐level risk‐graded thresholding scheme aligns alarms with safety‐consequence severity; and a ticket‐level task‐consistency check catches violations where all steps are locally correct but the ticket does not match the declared task. Experiments on 6842 tickets from 12 real substations achieve F 1 = 87.4% (+2.0% over the best 2025 SOTA baseline), 0.6‐step detection latency, 18.3‐ms single‐step inference, 91.2% top‐3 step localisation and only 3.6% F1 drop on three unseen substations.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Emerging AI for resilient smart-grid fault detection: an evidence-based capability synthesis, maturity assessment, and research roadmapJournal of Electrical Systems and Information Technology · 2026
- Graph-Based Dynamic Activity Prediction for Real-Time Power System ApplicationsarXiv · 2026
- An Intelligent Predictive Maintenance Architecture for Substation Automation: Real-World Validation of a Digital Twin and AI Framework of the Badra Oil Field ProjectElectronics · 2026
- Structure-generalizable large models for power system operation under topology uncertainty: A graph-based foundation learning frameworkApplied Energy · 2026
- Construction Method for a Domain-Specific LLM for Substation Safety Hazard Diagnosis Based on a Bilateral Dual-Branch Dual-LoRA ArchitectureElectronics · 2026
- Digital twin-driven fault diagnosis of power substations by multi-modal fusion learningNature Communications · 2026