Coordinated Control Strategy for Power Quality in Microgrids With Multiple Parallel Inverters
Peng Wang
Key points
From the paper's conclusion- Compared to the time‐triggered control strategy, the communication times can be reduced by 77%, and the response speed in reactive power sharing can be reduced by 1.3 s.
Abstract
To address the lack of coordination among frequency restoration, voltage restoration, reactive power sharing, and voltage unbalance compensation in islanded microgrids with multiple distributed generators (DGs) under unbalanced load conditions, this paper proposes a coordinated control strategy for DGs and a static var generator (SVG) based on a networked hierarchical control architecture. The proposed control framework consists of a local control layer and a distributed secondary control layer. In the local control layer, droop control, dual‐loop voltage/current control, and selective virtual impedance are employed to ensure stable system operation and proper reactive power sharing. In the distributed secondary control layer, an event‐triggered consensus‐based control strategy is developed to achieve frequency restoration, voltage restoration, and coordinated reactive power regulation while reducing communication burden without compromising control performance. Furthermore, a coordinated DG–SVG compensation mechanism is proposed to dynamically allocate voltage unbalance and reactive power compensation according to the compensation capability of the DGs. When the compensation capability of the DGs becomes insufficient, the SVG is activated to provide supporting compensation, thereby avoiding excessive reliance on a single compensation device and improving the overall voltage quality and compensation capability of the microgrid. The simulation results show that the proposed control strategy can achieve the rapid recovery of frequency and voltage, and the effective suppression of voltage unbalance. Compared to the time‐triggered control strategy, the communication times can be reduced by 77%, and the response speed in reactive power sharing can be reduced by 1.3 s. It can still maintain good performance in a nonideal communication environment.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Communication-efficient distributed secondary control for accurate reactive and harmonic power sharing in stand-alone AC microgrids under switching communication topologiesScientific Reports · 2026
- Fully Distributed Event-Triggered Secondary Control for Islanded Microgrid Restoration With Communication Link FaultsIEEE Transactions on Automation Science and Engineering · 2026
- A Hybrid LQR–PI Control Strategy with Virtual Impedance for Next-Generation Inverter-Based Microgrids: Enhanced Dynamic Stability and Power QualityEnergies · 2026
- Distributed Optimal Control of AC Microgrids with Coupled Voltage and Frequency RegulationEnergies · 2026
- Multi-objective integrated VSG control strategy under unbalanced conditionsCircuit World · 2026
- Coordinated capacitor-SVG reactive power compensation configuration for substations with high-penetration distributed photovoltaic integrationJournal of Renewable and Sustainable Energy · 2026