Monitoring building HVAC runtime using low-cost acoustic sensors.
Kieren H McCord, Laura Fierce, Paul Francik, Chrissi A Antonopoulos
Pacific Northwest National Laboratory, Richland, Washington 99354, USA.
Key points
From the paper's conclusion- We demonstrate and evaluate this approach in a full-scale laboratory home designed for energy performance testing.
Abstract
This paper evaluates whether low-cost acoustic sensors can be used to predict HVAC on/off state and runtimes by comparing acoustically inferred air handler unit (AHU) operation with power level measurements from a dedicated AHU circuit. We demonstrate and evaluate this approach in a full-scale laboratory home designed for energy performance testing. A threshold-based state inference algorithm applied independently to the power and noise data showed 96.8% agreement, suggesting that overall A-weighted sound level can be used to estimate AHU state for two-state systems with careful sensor placement.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Online Identification Can Replace a Floor-Plan Prior on Unseen BuildingsarXiv · 2026
- An Artificial-Intelligence-Based Predictive Maintenance Strategy Using Long Short-Term Memory Networks for Optimizing HVAC System Performance in Commercial BuildingsBuildings · 2025
- A Proposed Mamba Network for Multi-Horizon Prediction of Occupant Air-Conditioning BehaviorBuildings · 2026
- Adaptive Control of HVAC Systems in Public Buildings Under Dense Crowds: A Review of Synergistic Strategies for Thermal Comfort and Energy SavingEnergies · 2026
- Quantifying the impact of occupancy sensor errors on energy savings, thermal comfort, and peak demand in residential smart thermostatsJournal of Building Performance Simulation · 2026
- An annotated dataset of Building Management System periodic alarms.Data in brief · 2026