A Grey-Box Framework for Modeling Free-Floating Indoor Temperature and Cooling Implications in Residential Buildings in Hot-Arid Regions
Hamidreza Najafi, AbdMonem H. Beitelmal
Florida Institute of Technology · Hamad bin Khalifa University
Key points
From the paper's conclusion- The proposed grey-box framework achieved a one-step-ahead validation root-mean-square error (RMSE) of 0.083 °C and a mean absolute error (MAE) of 0.069 °C, while recursive simulations reproduced prolonged free-floating indoor temperature evolution with an average RMSE of approximately 1.16 °C over extended periods.
Abstract
Abstract In the present article, a data-driven, physics-informed case study of passive thermal behavior in a two-storey residential villa located in Al Rayyan, Qatar, is presented to characterize the building's thermal response and evaluate comfort-related cooling implications. During the monitoring periods, the villa operated under free-floating conditions with no active cooling, allowing the observed indoor temperature evolution to be attributed primarily to envelope-driven heat gains associated with outdoor conditions and solar irradiation. High-resolution measurements of indoor and outdoor air temperatures and relative humidity were collected at 5-min intervals over multiple summer periods. A low-order grey-box model, formulated in a lumped-capacitance (RC) framework, is developed and validated to predict indoor air temperature dynamics using measured indoor thermal state and a diurnal solar forcing proxy that captures thermal lag effects characteristic of heavy-mass construction. The resulting model enables the time-resolved prediction of indoor temperature evolution under free-floating conditions and is subsequently applied recursively to evaluate comfort-related cooling implications associated with common indoor setpoints. The proposed grey-box framework achieved a one-step-ahead validation root-mean-square error (RMSE) of 0.083 °C and a mean absolute error (MAE) of 0.069 °C, while recursive simulations reproduced prolonged free-floating indoor temperature evolution with an average RMSE of approximately 1.16 °C over extended periods. Recursive exceedance analysis showed that indoor temperatures remained above a 25 °C comfort threshold for more than 110 h during the analyzed monitoring periods, corresponding to approximately 443 °C h of cumulative thermal exposure. The proposed framework provides a practical pathway for translating field measurements into simplified predictive models that support passive thermal assessment and cooling-related analysis in hot-arid residential buildings.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- From BIM and white-box models to grey-box models: Model identification and long-horizon prediction of building thermal dynamicsE3S Web of Conferences · 2026
- The role of passive design strategies in achieving net-zero energy buildings: The solar nursery in Baghdad as a case studyE3S Web of Conferences · 2026
- Integrating bioclimatic features in building energy modelling to study thermal performance of a naturally ventilated hostel building in the composite climate zone of IndiaAdvances in Building Energy Research · 2026
- Quantifying the Energy Performance of Biomimetic Façade Systems in Hot–Arid Residential Buildings: A Libyan Case StudyBuildings · 2026
- Residential Performance Gaps in UAE Villas: A Critical Review of Envelope Performance, Occupant Adaptation and Sustainable HousingSustainability · 2026
- Indoor temperature and humidity prediction in residential buildings: A review of the white box and black box modeling techniquesBuilding and Environment · 2025