A High-Pressure Drum-Evaporators in Combined Cycle Power Plants Hybrid Thermodynamic Modelling and Calibration Framework for simulation of cyber-physical threats
Nunziata Alessio, Giardiello Giovanni, Gimelli Alfredo, Langella Giuseppe, Adinolfi Giovanna, Valenti Maria
Key points
From the paper's conclusion- The results demonstrate that the reduced-order model preserves the principal thermofluid mechanisms needed for monitoring, off-design simulation, control studies, and virtual-sensing applications.
Abstract
The increasing cycling duty of combined-cycle power plants requires models that can reproduce the coupled thermal and hydraulic response of heat recovery steam generators without the computational burden of a fully distributed plant model. This study develops and evaluates a nonlinear lumped-parameter model of the high-pressure natural-circulation evaporator and steam-drum subsystem of an industrial heat recovery steam generator. The formulation combines a physically resolved representation of evaporation, flash generation, metal thermal storage, and natural circulation with the four-state drum-boiler structure required to reproduce pressure and shrink-and-swell dynamics. Heat transfer from the gas-turbine exhaust is evaluated using an effectiveness-NTU relation with a load-dependent overall heat-transfer coefficient. The model was calibrated against 32 distributed-control-system operating points recorded over approximately eight hours at 15-min intervals. Three physically interpretable multipliers were estimated by Nelder-Mead optimization: equivalent metal mass, riser internal volume, and a global thermal-efficiency factor. The calibrated model achieved R2 = 0.9800, RMSE = 1.33 bar, and MAPE = 1.05% for drum pressure. Steam mass flow, which was not included in the calibration objective, was reproduced with R2 = 0.9789, RMSE = 0.85 kg/s, and MAPE = 1.07%; all operating points fell within a preselected +/-5% band. The average heat input of 81.3 MW corresponded to a potential steam generation of 61.4 kg/s, compared with 61.1 kg/s measured at the outlet. The results demonstrate that the reduced-order model preserves the principal thermofluid mechanisms needed for monitoring, off-design simulation, control studies, and virtual-sensing applications. Limitations associated with in-sample pressure calibration and sparse quasi-steady measurements are explicitly discussed.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Physics-Based Dynamic Modeling of Hydro Generator Cooling System Using Plant Data, Empirical Heat Transfer Correlations and Reduced Parameter EstimationDynamics · 2026
- A Study on Dynamic Analysis and Operational Optimization of an F-Class Combined-Cycle Power Plant Under Seasonal Load ConditionsApplied Sciences · 2026
- When Does a Two-Node Thermal Model Suffice? An Evidence-Graded Reduced-Order Benchmark for the KRUSTY Heat-Pipe Microreactor TestApplied Sciences · 2026
- Comparing Heat Extraction from PWR-SMR and HTGR Power Cycles for Hydrogen and Sustainable Aviation Fuel ProductionEnergies · 2026
- Performance Assessment of Model-Based Controlled Organic Rankine Cycle System for Waste Heat RecoveryJournal of energy resources technology. · 2026
- Optimization of a Heat Recovery Steam Generator Inlet Duct for Flow Uniformity Improvement Based on a Surrogate-Assisted CFD MethodEnergies · 2026