Assessment and optimization of a controlled mechanical ventilation system for improving Indoor Environmental Quality in school buildings

Leonardo Guglielmi, Samantha Di Loreto, Matteo Falone, Sergio Montelpare, Mariano Pierantozzi

Key points

From the paper's conclusion
  • The results show that, in the current configuration, the CMV system improves hygrothermal stability but does not yet ensure fully satisfactory air-quality conditions throughout the classroom volume.

Abstract

This work assesses the performance of a controlled mechanical ventilation (CMV) system installed in a classroom of the “Isabella Gonzaga“ secondary school in Chieti, within the “NecessARIA” project. The aim is to verify the system’s ability to ensure adequate Indoor Environmental Quality (IEQ) conditions in terms of hygrothermal comfort and indoor air quality, with particular reference to the CO 2 concentration as a proxy for effective air renewal. The adopted methodology combines in-situ experimental measurements with finite-element numerical simulations developed in COMSOL Multiphysics, enabling a detailed modelling of the thermofluid dynamic phenomena induced by the ventilation system. The numerical analysis enabled the evaluation of the spatial distribution of airflows and pollutants within the classroom, identifying criticalities related to the non-uniformity of ventilation and the persistence of poorly ventilated zones. The results show that, in the current configuration, the CMV system improves hygrothermal stability but does not yet ensure fully satisfactory air-quality conditions throughout the classroom volume. On this basis, the design-optimization strategies required to achieve IEQ conditions suitable for supporting occupants’ well-being and learning are discussed.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers