Access Control and HVAC Operation Strategies for Preventive Conservation: A Monitoring Campaign in a Sicilian Museum
Maria La Gennusa, Giada Rita Licciardi, Giorgia Peri, Gianluca Scaccianoce
Key points
From the paper's conclusion- The findings demonstrate that visitor access control can be used as an active environmental management tool, reducing short-term microclimatic fluctuations and supporting the achievement of preventive conservation objectives.
Abstract
Visitor occupancy is a major driver of indoor environmental variability in museums, affecting temperature, relative humidity, air quality, and ultimately the preservation of cultural heritage collections. Although several approaches have been proposed to mitigate visitor-induced disturbances, a structured classification of visitor access control strategies and their integration with environmental management are still limited. This study investigates the relationship between visitor dynamics and HVAC operation through a monitoring campaign conducted in eight exhibition halls of the Galleria d’Arte Moderna (GAM) of Palermo. A review of the scientific literature and relevant standards was first carried out to identify and classify existing visitor access management approaches, leading to the development of a preliminary taxonomy of access control strategies. Building on this analysis, a predictive access control model based on occupancy propagation and dynamic capacity constraints was proposed. The results show that the carrying capacity of museum spaces should not be considered a fixed parameter but rather a dynamic function of HVAC responsiveness and outdoor climatic conditions. A maximum occupancy function, n max (T out ), was introduced to link visitor management with HVAC system performance. The findings demonstrate that visitor access control can be used as an active environmental management tool, reducing short-term microclimatic fluctuations and supporting the achievement of preventive conservation objectives. The proposed approach provides a basis for integrating visitor flow regulation with environmental control strategies in museum environments.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Adaptive Control of HVAC Systems in Public Buildings Under Dense Crowds: A Review of Synergistic Strategies for Thermal Comfort and Energy SavingEnergies · 2026
- Micro-Behavioral Load Decoding and Spatial Behavioral Signature Recognition in Museums Using Natural VideosHeritage · 2026
- Smart Archival Box: A Hybrid Active–Passive Microclimate Control System for Preventive Conservation of Archival and Museum CollectionsApplied Sciences · 2026
- A Damage-Spectrum Framework for Specifying the Indoor Climate of Historic BuildingsBuildings · 2026
- Transient wake and cross-zone exchange induced by human doorway crossing: A manifold-learning analysisPhysics of Fluids · 2026
- Applicability of Site-Level Operational and Environmental Information for Long-Term Heritage Timber Monitoring: Vibration Response and Tilt-Monitoring Baselines at Xuankong TempleBuildings · 2026