Integrated intelligent smoke management system: integrating electrostatic precipitation with PID-controlled air recirculation for charcoal-grill restaurant kitchens
Sutipong Chumkhuntod, Anantakul Intarapadung, Karin Kandananond
Key points
From the paper's conclusion- These findings demonstrate that integrating a dual-stage ESP with PID-controlled multi-pass air recirculation improved particulate-removal performance under the specific experimental conditions investigated.
Abstract
Charcoal-grill restaurants can contribute to localized air pollution through emissions of particulate matter, including PM₂.₅ and PM₁₀, particularly in small kitchens with limited ventilation. This study developed and experimentally evaluated an intelligent smoke management system integrating a dual-stage electrostatic precipitator (ESP), PID-controlled multi-pass air recirculation, and a compact smoke-capture hood for small charcoal-grill restaurants. The prototype was tested in an enclosed kitchen with a volume of 25 m 3 under Single-pass and Recirculation operating modes at airflow velocities of 2 and 3 m/s using six paired experimental runs (n = 6). System performance was evaluated based on PM₂.₅ and PM₁₀ removal efficiency, particulate removal rate, Equivalent Clean Air Delivery Rate (CADRₑq), and electrical energy consumption. The results showed that the Recirculation mode at an airflow velocity of 3 m/s achieved the highest particulate-removal efficiencies, reaching 95.15% for PM₂.₅ and 95.50% for PM₁₀. These values were significantly higher than those obtained under the corresponding Single-pass condition (p < 0.001). Under this operating condition, the measured average system-level electrical power was 68.2 W, corresponding to an energy consumption of 11.4 Wh per 10-min experimental cycle. The equivalent Clean Air Delivery Rate (CADRₑq), estimated from the experimentally derived airflow and measured particulate-removal efficiency, was approximately 813.1 m 3 /h for PM₂.₅ and 816.1 m 3 /h for PM₁₀. These findings demonstrate that integrating a dual-stage ESP with PID-controlled multi-pass air recirculation improved particulate-removal performance under the specific experimental conditions investigated. However, because the system was evaluated at a single test site using six matched experimental runs, further validation across different kitchen environments and cooking loads, together with direct ozone and VOC measurements and long-term operational assessment, is required before broader commercial applicability can be established.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Indoor Air Quality and Exposure Characterization in Operational Waterpipe Cafés: Field Measurements of Particulate and Volatile Pollutants in Al‐Madinah Al‐MunawwarahIndoor Air · 2026
- Combustion-derived air pollution and heat from gas-fired appliances in commercial kitchens can exceed health-based guidelinesEnvironmental Research Letters · 2026
- Cooking fuels and household air pollution in resource-constrained urban environments: A field assessmentEnergy Sustainable Development/Energy for sustainable development · 2026
- Chemical and toxicological assessment of particulate matter in a charcoal barbecue restaurant.Environmental toxicology and pharmacology · 2026
- Indoor atmospheric nanoparticle emissions, inhalation exposures, and indoor-to-outdoor transport during residential activities with electric and combustion appliancesJournal of Hazardous Materials · 2026
- Measurements of Volatile Organic Compounds and Aerosols from Cooking during the CLEAN Home Indoor Field StudyACS ES&T Air · 2026