Evaluating Individual Infection Risk: The Interplay between Air Mixing Intensities and Occupant Dynamics.
Hamed Sobhani, Gautam Vanama, Shengwei Zhu, Jianyu Lai, Kristen K Coleman, Donald K Milton, Jelena Srebric
Department of Mechanical Engineering, University of Maryland, College Park, Maryland20740, United States. · Department of Global, Environmental, and Occupational Health, University of Maryland, College Park, Maryland20742, United States.
Key points
From the paper's conclusion- We propose a Reynolds number (Re)-based modeling guideline: steady-state CFD-CV for moderate mixing (900 ≤ Re ≤ 2300), a well-mixed assumption for high mixing (Re > 2300), and transient CFD-CV for low mixing (500 ≤ Re < 900) during breathing and speaking, and steady-state CFD-CV for coughing and sneezing regardless of Re value.
Abstract
Aerosol transmission remains a critical route for the spread of respiratory infectious diseases, yet real-time exposure mapping in complex public spaces is computationally demanding. This study presents a robust and adaptable framework for estimating dynamic individual exposure (i.e., viral dose) by integrating high-fidelity computational fluid dynamics (CFD) with computer vision (CV) analysis. By overlaying validated steady-state viral aerosol plumes onto dynamic human interaction data, we evaluated the interplay between airflow patterns and human behaviors under two distinct air change rates (ACH: 25 h-1 and 3 h-1). Each scenario was simulated both with and without MERV-13 filtration. Applications in both a stochastic-movement hotel meeting room and a stationary-occupant office demonstrate that while high turbulence due to high ACH limits the spatial extent of plumes, sustained close proximity in structured settings can result in disproportionately high viral doses for specific individuals. MERV-13 filtration effectively reduced exposure within high-concentration zones. We propose a Reynolds number (Re)-based modeling guideline: steady-state CFD-CV for moderate mixing (900 ≤ Re ≤ 2300), a well-mixed assumption for high mixing (Re > 2300), and transient CFD-CV for low mixing (500 ≤ Re < 900) during breathing and speaking, and steady-state CFD-CV for coughing and sneezing regardless of Re value. This framework supports real-time monitoring and targeted interventions, providing a data-driven foundation for indoor occupant safety.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Multi-Scale Computational Fluid Dynamics Investigation of Ventilation-Controlled and Gravity-Controlled Respiratory Aerosol Transport in an Office Environment: Implications for Heating, Ventilation, and Air Conditioning Design and Airborne Infection MitigationBuildings · 2026
- Quantitative Microbial Risk Assessment of Airborne Viruses and Semi-Quantitative Bacterial Risk Scoring in Occupied European Indoor Environments: A Multi-Country StudyMicroorganisms · 2026
- Quantifying the impact of 3D diffusion and local versus global removal by surface deposition on indoor airborne transmissionarXiv · 2026
- Heterogeneity of Airborne Virus Transmission in the Built Environment: A Narrative Review.Pathogens & immunity · 2026
- Modeling and Experimental Validation for Detecting Indoor Respiratory Droplet.Biosensors · 2026
- CFD Modeling of Airflow and Aerosol Transport in the Human Respiratory System: A Comprehensive ReviewPharmaceutical Research · 2026