From the paper's conclusion
  • Overall, the findings demonstrate that CSA provides a reliable and computationally competitive approach for DG allocation in radial distribution networks, although its performance should be assessed against alternative metaheuristic algorithms and under realistic operating uncertainties.

Abstract

This study investigates the optimal placement and sizing of distributed generation (DG) units in radial distribution networks using a crow search algorithm (CSA) integrated with the backward/forward sweep (BFS) load-flow method. A multi-objective optimization framework based on a weighted-sum formulation is developed to minimize active and reactive power losses, voltage magnitude deviations, and steady-state voltage-angle deviations while satisfying bus-voltage, line thermal, DG capacity, and installation constraints. The performance of CSA is comparatively evaluated against particle swarm optimization (PSO), differential evolution (DE), and the grey wolf optimizer (GWO) through 30 independent runs under identical computational budgets on the IEEE 33-bus test system, with additional validation on the IEEE 69-bus system. For the IEEE 33-bus network, considering three DG units operating at a 0.95 power factor and a combined capacity of 1500 kW, CSA identifies buses 13, 25, and 30 as the optimal installation locations. The resulting configuration reduces active power losses from 202.68 to 70.06 kW and reactive power losses from 135.14 to 47.58 kVAr, corresponding to reductions of 65.4% and 64.8%, respectively. Furthermore, the minimum bus-voltage magnitude improves from 0.9131 to 0.9500 p.u., while the minimum static voltage stability index increases from 0.695 to 0.815. Comparative results indicate that all four algorithms identify practically equivalent best solutions. CSA achieves feasible solutions in all 30 independent runs, whereas PSO fails to produce feasible solutions in five runs. Nevertheless, DE and GWO demonstrate slightly better mean objective values than CSA, with improvements of 0.4% and 0.3%, respectively, indicating that CSA is competitive but does not establish overall superiority. A 1000-sample Monte Carlo assessment further reveals the sensitivity of the optimized configuration to variations in load demand and DG output, with the minimum voltage remaining at or above 0.95 p.u. in only 4.3% of the simulated scenarios. The observed voltage-angle deviations remain within approximately 1.1° and are interpreted exclusively as steady-state performance indicators rather than evidence of dynamic stability. Overall, the findings demonstrate that CSA provides a reliable and computationally competitive approach for DG allocation in radial distribution networks, although its performance should be assessed against alternative metaheuristic algorithms and under realistic operating uncertainties.

Read the paper

Discussion

Science Skim's AI key points, plus readers' public thoughts

Readers' thoughts

No reader thoughts yet.

Related papers