Electro‐Thermal Performance and System‐Level Coefficient of Performance Correlation of Flat and Corrugated Thermoelectric Radiant Ceiling Cooling Panels
Gaurav Mishra, Satyendra Prajapati, Jyotirmay Mathur, Aneesh Prabhakar
Key points
From the paper's conclusion- This study experimentally investigates flat and corrugated TERP arrays in a 2.8 × 2.8 × 3 m 3 outdoor test chamber with a 3.07 m 2 active ceiling comprising 12 panels connected in a 4S3P configuration.
Abstract
Buildings account for a significant share of global energy consumption, with HVAC systems responsible for over one third of building energy use. Increasing cooling demand has accelerated interest in refrigerant‐free thermoelectric radiant ceiling panels (TERPs). However, the influence of corrugated surface geometry on large‐scale TERP performance and predictive design methods remains limited. This study experimentally investigates flat and corrugated TERP arrays in a 2.8 × 2.8 × 3 m 3 outdoor test chamber with a 3.07 m 2 active ceiling comprising 12 panels connected in a 4S3P configuration. Experiments were performed at supply voltages of 32, 36, and 40 V. The optimum corrugated geometry, with a 150° corrugation angle and a 310 mm fold length, achieved the lowest surface thermal resistance of 0.411 K/W and increased effective surface area by 3.5%. Compared with the flat panel, the optimized corrugated TERP increased cooling capacity by 10.4%, reaching 130.76 W/m 2 at 40 V, while reducing the temperature nonuniformity coefficient by 31%. It also improved the coefficient of performance (COP) by 5.2%, 8.2%, and 16.5% at 32, 36, and 40 V, respectively. An empirical dimensionless COP correlation for corrugation angles of 60°–180° was developed and validated, providing a practical tool for designing high‐performance TERP systems for energy‐efficient cooling.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Thermal modeling of a rotary heat pump: effects of key parameters on performanceInternational Journal of Air-Conditioning and Refrigeration · 2026
- Reliably characterizing the performance of thermoelectric coolersReview of Scientific Instruments · 2026
- Multi-Physic Coupling Analysis and Structure Optimization of Vehicle Thermoelectric RefrigeratorsApplied Sciences · 2026
- Experimental evaluation of radiant ceiling panels in office building perimeter zonesEnergy and Buildings · 2025
- Accurate Measurement and Thermal Correction of Cooling Performance for Thermoelectric Cooling Devices: Heat Compensation Method.Small methods · 2026
- Experimental evaluation of a R290 vapour compression refrigeration system hybridised with a thermoelectric subcoolerEnergy Conversion and Management · 2026