Performance Analysis of the Finned Heat Sinks Used in the Immersion Cooling System of Data Center
Lei Zhao, Xiaosong Cheng, Hongqiang Ma, Yulong Yang, Wei Cui, Jiajun Wang, Cuiwei Liu
Key points
From the paper's conclusion- Therefore, a boiling heat transfer model is developed for the finned heat sink.
Abstract
Two‐phase immersion liquid cooling system (TPICS) is an effective method to solve the heat dissipation requirements in data centers. However, the influence of different CPU loads and cross‐sectional profiles of fins on boiling heat transfer characteristics remains insufficiently understood. The main aim of the study is to investigate the boiling characteristics of coolant in finned heat sinks under different CPU loads and propose an optimized fin structure to improve heat transfer performance and energy efficiency. Therefore, a boiling heat transfer model is developed for the finned heat sink. The simulation results are validated against experimental data from the literature. The relative error is within ±15%. Two typical operating scenarios, low power and high power, are covered in this study. Meanwhile, a comparative evaluation is conducted on the thermal performance of the rectangular fin and the novel fin configuration. The quantitative results are as follows. The maximum fin temperature reaches 49.3°C at the lateral position of z = 65 mm under the low‐power condition. This is only 0.3°C higher than the coolant boiling point, and natural convection alone is sufficient to meet the CPU heat dissipation demand. The maximum fin temperature of 54.6°C occurs at the fin base under the high‐power condition. The vapor volume fraction distribution reveals that boiling heat transfer is nearly absent on both sides of the upper fin region. Accordingly, a novel circular segment fin configuration is proposed to address this issue. Results show that the circular segment fin exhibits superior heat transfer performance under high‐power conditions. The optimized circular segment fin reduces the peak temperature by 2.8 K and material consumption by 27.3% compared with the rectangular fin.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Sustainable computational fluid dynamics optimization of heat sink performance for energy efficient device coolingScientific Reports · 2026
- Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centersCase Studies in Thermal Engineering · 2026
- Multi-objective optimization of a microchannel pin-fin hybrid heat sink based on CFD and NSGA-II genetic algorithmCase Studies in Thermal Engineering · 2025
- Performance of Fin Enhanced Compact Heat Exchanger Using Experimental AnalysisSciEn Conference Series Engineering · 2026
- Comprehensive assessment of coolants used single-phase immersion cooling data centerEnergy · 2025
- Ultra-low thermal resistance and pressure drop copper and copper-tungsten diamond-shaped pin fin cold plates for liquid cooling of electronicsInternational Journal of Heat and Mass Transfer · 2025