Numerical Investigation of the Thermal–Hydraulic Performance of a Double‐Pipe Heat Exchanger With Porous Inserts
S. B. Anjappa, Shivaranjini, K. Ganesh, Mohit Kumar Agrawal, Umesh Gupta, Prabhukumar Sellamuthu
Key points
From the paper's conclusion- These results demonstrate that segmented, staggered copper‐foam inserts provide an effective passive enhancement technique for compact, energy‐efficient DPHEs used in thermal energy storage, waste heat recovery, heating, ventilation, and air conditioning (HVAC) systems, and the process industry.
Abstract
Double‐pipe heat exchangers (DPHEs) are widely used because of their simple design, operational reliability, and effective heat‐transfer capability. This study presents a three‐dimensional computational fluid dynamics (CFD) analysis of a counterflow DPHE fitted with interrupted and staggered (St.) segmented copper‐foam inserts in the annular region. Numerical simulations were performed using ANSYS Fluent, employing the Darcy–Brinkman–Forchheimer porous media model coupled with the local thermal nonequilibrium energy model to accurately predict the fluid flow and heat transfer within the porous structure. Ten porous configurations, comprising interrupted and staggered arrangements with different segment arrangements and configurations, were evaluated over a Reynolds number range of 205–1435. The thermo‐hydraulic performance was assessed using the Nusselt number, friction factor, and thermal performance factor (TPF). Compared with the smooth annulus, the interrupted configurations increased the average Nusselt number by 269.3%–293.7%, whereas the staggered configurations increased it by 308.6%–389.1%. These improvements were accompanied by an increase in the friction factor of 196.1%–213.5% and 259.6%–372.9%, respectively. Despite the additional pressure loss, all configurations produced TPF values greater than unity, ranging from 2.58 to 2.71 for interrupted arrangements and 2.70 to 3.00 for staggered arrangements, confirming an overall improvement in the thermo‐hydraulic performance. Although the optimum configuration varied with Re , the St.‐3–11 arrangement delivered the best overall performance across the investigated range, whereas St.‐3–5 achieved the highest TPF at Re = 205. These results demonstrate that segmented, staggered copper‐foam inserts provide an effective passive enhancement technique for compact, energy‐efficient DPHEs used in thermal energy storage, waste heat recovery, heating, ventilation, and air conditioning (HVAC) systems, and the process industry.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Thermal and Flow Characteristics of Perforated Blockages in Confined ChannelsAerospace · 2026
- A Comprehensive Investigation Of Shell And Tube Heat Exchangers Based On Porous Baffle Design And Multi-Objective Parameter OptimizationInternational Journal of Thermal Sciences · 2025
- Flow dynamics mechanisms and thermal hydraulic performance evaluation of triply periodic minimal surface (TPMS) heat exchangersPhysics of Fluids · 2026
- A Systematic Investigation of the Effect of Port Diameter on the Thermal Performance of a Corrugated Plate Heat ExchangerMathematics · 2026
- Passive Techniques for Heat Transfer Enhancement in Selected Industrial Heat Exchangers: A Comprehensive Review of Geometric Modifications and NanofluidsThermo · 2026
- Fluid and thermal flow in annular side of the double twisted helically coiled tubes heat exchangers under various configurationsInternational Journal of Air-Conditioning and Refrigeration · 2025