Key points
From the paper's conclusion- Compared with the two‐level DVR, the three‐level NPC‐based DVR reduced the PMSG terminal‐voltage THD from 0.41%–0.62% to 0.28%–0.54% under the investigated voltage‐sag faults and from 0.36%–0.53% to 0.19%–0.48% under asymmetric and symmetric voltage‐swell conditions.
Abstract
This paper introduces a protection scheme for a grid‐connected wind‐turbine power‐conversion system employing a Permanent Magnet Synchronous Generator (PMSG), a dynamic voltage restorer (DVR), and a battery energy storage system (BESS). The BESS is integrated into the DC‐link through a bidirectional buck‐boost converter (BBBC) to support voltage regulation during wind‐speed fluctuations and grid disturbances. Particle swarm optimization (PSO) is used offline to tune the BBBC PI‐controller parameters, improving DC‐link voltage regulation through BESS charging and discharging. The AC side of the DVR is connected in series with the PMSG terminal, while its DC side is coupled to the DC bus. A three‐level Neutral Point Clamped Multi‐Level Inverter (NPC‐MLI) is employed for the DVR and is activated during voltage sags and swells affecting the terminal voltage. The proposed scheme was evaluated using MATLAB/Simulink under varying wind speeds and different grid‐disturbance conditions. Compared with the two‐level DVR, the three‐level NPC‐based DVR reduced the PMSG terminal‐voltage THD from 0.41%–0.62% to 0.28%–0.54% under the investigated voltage‐sag faults and from 0.36%–0.53% to 0.19%–0.48% under asymmetric and symmetric voltage‐swell conditions. Moreover, compared with the conventional PI controller, the PSO‐tuned PI controller reduced DC‐link voltage overshoot and undershoot under wind‐speed variation, voltage sag, and voltage swell conditions, while providing shorter settling times during voltage sag and swell and maintaining the DC‐link voltage close to its reference throughout the investigated wind‐speed variations. These improvements were demonstrated in MATLAB/Simulink for the investigated parameter set and disturbance scenarios.
Read the paper
Discussion
Science Skim's AI key points, plus readers' public thoughts
Readers' thoughts
No reader thoughts yet.
Related papers
- Optimal placement of DSTATCOMs and PID tuned controller in IEEE bus system for enhanced voltage stability and power loss reduction under RES integration using hybrid BWO-SSA algorithmResults in Engineering · 2025
- Power Quality Enhancement of a Grid-Connected PV–WECS Hybrid Energy Storage System Using Fuzzy Logic Controller and Dynamic Voltage RestorerInternational Journal for Research in Applied Science and Engineering Technology · 2026
- Enhanced jellyfish search-optimized cascaded fuzzy-FOPI control of a three-phase dynamic voltage restorer for power quality improvementScientific Reports · 2026
- Modeling and dq-Axis Control of a Unity Power Factor and DC-Link Voltage Regulated Grid-Connected: Permanent Magnet Wind Energy Conversion System of Synchronous GeneratorJournal of Intelligent Decision Making and Information Science · 2026
- Reactive power regulation of power system using an SVC with fixed, optimized, and CNN-based PI controllersMultiscale and Multidisciplinary Modeling, Experiments and Design · 2026
- Enhanced Fault Ride-Through of Grid-Connected PV Systems Using PIR-MPC-Controlled Supercapacitor Energy StorageEngineering Research Express · 2026